Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03097 Rough-In Permanent Service8/24/20058/25/20058/25/2005 4:39:34 PMPPASS
darrell ###-#### ok to final
ELE05-01922 Final8/25/20058/25/20058/25/2005 4:39:06 PMPPASS
Scheduled by a contractor via Hello! on 8/25/2005 at 7:30:02 AM. Contact: ###-####. ok to final
ELE05-01721 Final8/25/20058/25/20058/25/2005 3:50:44 PMPPASS
donna; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE05-02971 Electrical Rough-In8/24/20058/25/20058/25/2005 3:34:46 PMPPASS
CONTACT: CASEY WILDE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ric ok, p/s u/g n ok
ELE05-02451 Final8/25/20058/25/20058/25/2005 2:27:54 PMPPART
Ready for final, please contact Duane, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters checked facility, told contr to add lock-out for dishwasher. they will wire in air compressor and call for final. signed t/o card
ELE05-03106 Rough-In Permanent Service8/24/20058/25/20058/25/2005 1:12:45 PMPCANC
###-#### warren see ri
ELE04-03888 Final8/25/20058/25/20058/25/2005 12:44:11 PMPPART
Scheduled by a contractor via Hello! on 8/25/2005 at 8:58:49 AM. Contact: ###-####. clg cover ok, will need to check door openers later,
ELE05-03104 Electrical Rough-In8/24/20058/25/20058/25/2005 11:52:44 AMANH
electric rough in. thank you; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called and said to re-schedule
ELE05-03113 Final8/25/20058/25/20058/25/2005 11:13:11 AMPCANC
FINAL FOR A/C UNIT CIRCUIT; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH Inspection cancelled from web by: BRIAN KEITH
ELE05-03062 Final8/24/20058/25/20058/25/2005 9:54:18 AMAPASS
please call 30min prior///becky; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa signed struct card, ok to final
ELE05-03093 Electrical Rough-In8/24/20058/25/20058/25/2005 9:24:34 AMAPASS
monty; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made, called and told to change one box. ric ok
ELE05-03109 Temporary Service8/24/20058/25/20058/25/2005 8:56:48 AMAFAIL
stu ###-#### called contr, left corr notice, fee due, 590.6(B)(1) gfci protection shall be provided for recpts,408.4 circuit directory shall be provided, 312.5 abrasion protection shall be provided for gec, BCC job id sticker shall be posted
ELE05-02227 Final8/24/20058/25/20058/25/2005 8:10:53 AMPCANC
CONTACT: ALEX KELLY; Phone #: ###-#### Internet Inspection Request from: Deb McCoy Inspection cancelled from web by: Deb McCoy
ELE05-03042 Electrical Rough-In8/24/20058/25/20058/25/2005 8:04:42 AMAFAIL
TOBY WALL COVER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy nec 110.26(F)(1)(a),(b) no foreign piping syatems shall be installed in dedicated electrical space
ELE05-03106 Electrical Rough-In8/25/20058/25/20058/25/2005 12:00:00 AMPPASS
###-#### warren ric ok