ELE06-00711
| Electrical Rough-In | 8/25/2006 | 8/25/2006 | 8/25/2006 3:06:08 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 8/25/2006 at 8:07:49 AM. Contact: ###-####. egress stairs r/i ok
|
ELE06-03000
| Electrical Rough-In | 8/25/2006 | 8/25/2006 | 8/25/2006 2:33:38 PM | P | FAIL |
|
|
elmer; Phone #: ###-####/###-#### cell Internet Inspection Request from: Cathy Chiles corr. met owner 110.12(A) seal KOs replace pastic boxes with extra KOs broken out, 300.4 nail plates and 11/4", 230. 24(A) 8ft clearence over roof, 314.20 boxes shall be flush with siding outside fixture110.26 needs clearence for p/s, 314.43 no scfrews in plastic boxes, 330.40 use conn. listed for MC furnace,210.52or104(A)(1) grd or bond water 310.16 shall not use 14 on 20 amp circuit, note needs 2" rmc,or imc for mast, 3 way wiring all messed up wiring not ready partial corr. only told owner also makeup not done cow
|
ELE06-03156
| Final | 8/25/2006 | 8/25/2006 | 8/25/2006 1:22:20 PM | P | PASS |
|
|
burch - reinsp grounding; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok survey posted 250.64(B) shall protect or replace #8 GEC with #6
|
ELE06-03134
| Final | 8/25/2006 | 8/25/2006 | 8/25/2006 12:36:36 PM | P | FAIL |
|
|
corr. called 300.10 all fittings shall be made up tight, 314.15(A) shall use UL listed r/t fittings
|
ELE06-02851
| Final | 8/25/2006 | 8/25/2006 | 8/25/2006 12:35:13 PM | P | PASS |
|
|
dave (or ###-####); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok for perm. occupancy no card
|
ELE06-03156
| Final | 8/24/2006 | 8/25/2006 | 8/25/2006 11:10:01 AM | A | FAIL |
|
|
butch; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. called terminate all GEC at p/s not subpanel 250.24(A)(1) grd or bond water
|
ELE06-01402
| Final | 8/24/2006 | 8/25/2006 | 8/25/2006 11:08:40 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
|
ELE06-01130
| Final | 8/24/2006 | 8/25/2006 | 8/25/2006 11:08:19 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
|
ELE06-03000
| Rough-In Permanent Service | 8/24/2006 | 8/25/2006 | 8/25/2006 9:40:26 AM | A | NH |
|
|
elmer - as early as possible; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called left message notice posted
|
ELE06-02415
| Final | 8/25/2006 | 8/25/2006 | 8/25/2006 9:16:34 AM | A | PASS |
|
|
ok
|
ELE06-02415
| Rough-In Permanent Service | 8/24/2006 | 8/25/2006 | 8/25/2006 9:14:22 AM | A | PASS |
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs p/s o/h rec. ok
|
ELE06-03167
| Temporary Service | 8/24/2006 | 8/25/2006 | 8/25/2006 9:02:43 AM | A | PASS |
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley t/s o/h new ok
|
ELE06-02966
| Permanent Service | 8/24/2006 | 8/25/2006 | 8/25/2006 8:46:35 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/24/2006 at 5:35:42 PM. Contact: ###-####. p/s u/g new ok
|
ELE06-03166
| Rough-In Permanent Service | 8/24/2006 | 8/25/2006 | 8/25/2006 8:29:01 AM | A | CANC |
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs canceled by contr.
|
ELE06-03165
| Rough-In Permanent Service | 8/24/2006 | 8/25/2006 | 8/25/2006 8:25:36 AM | P | CANC |
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs canceled by contr.
|