ELE06-03141
| Electrical Rough-In | 8/25/2006 | 8/25/2006 | 8/25/2006 4:09:02 PM | P | PASS |
|
|
3 room addition Internet Inspection Request from: Rowdy Monroe called contr to add recpts, ric ok
|
ELE06-03182
| Electrical Rough-In | 8/25/2006 | 8/25/2006 | 8/25/2006 3:47:04 PM | P | PART |
|
|
adam Note: partial cover inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles soffit ok to cover
|
ELE06-03185
| Electrical Rough-In | 8/25/2006 | 8/25/2006 | 8/25/2006 3:08:00 PM | P | CANC |
|
|
need U/G inspection for cover. conduit will be installed by 1:30pm. if possible, please inspect after, thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH talked to elect, he asked to cancel said wanted shop to call for later inspection
|
ELE06-03166
| Rough-In Permanent Service | 8/25/2006 | 8/25/2006 | 8/25/2006 2:48:01 PM | P | FAIL |
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs called, left corr notice, nec 408.4 circuit directory shall be complete, concise , and explanatory for each circuit, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member, 406.5,110.12(C) recpt faceplate shall cover opening at recpt and no broken parts shall be used, 334.30 nm cable shall be supported within 12" of flex under bench, 110.26 access and working space shall be provided at panel, BCC no violations shall be retained(open splices over bench),strap flex into panel Note: ok to cover u/g, looked at feeder from in house, it is ok
|
ELE06-02906
| Electrical Rough-In | 8/25/2006 | 8/25/2006 | 8/25/2006 1:22:04 PM | P | PASS |
|
|
Craig; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr made, ric ok
|
ELE06-03171
| Conference | 8/24/2006 | 8/25/2006 | 8/25/2006 11:53:39 AM | A | DONE |
|
|
curtis - call prior to meet there; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley told contr u/g shall be inspected and concrete encased gec shall be supplied
|
ELE06-02496
| Final | 8/24/2006 | 8/25/2006 | 8/25/2006 10:52:00 AM | A | FAIL |
|
|
Internet Inspection Request from: Rowdy Monroe called left corr notice, nec 422.31(B) disconnect shall be supplied for heater, 110.3 gfci left of stove shall operate,BCC access shall be provided inside panel
|
ELE06-02668
| Electrical Rough-In | 8/24/2006 | 8/25/2006 | 8/25/2006 10:32:23 AM | A | PART |
|
|
eric - exterior conduit insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley u/g from street side pole base to sidewalk only ok to cover, cnd going to bldg has 3 90s from west pole base and is just under sidewalk bldg side
|
ELE06-03109
| Rough-In Permanent Service | 8/24/2006 | 8/25/2006 | 8/25/2006 9:59:35 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ric ok, p/s u/g n ok
|
ELE06-03179
| Electrical Rough-In | 8/24/2006 | 8/25/2006 | 8/25/2006 9:54:12 AM | A | FAIL |
|
|
jeremy; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left message, nec 517.13(A) metal raceways shall be provided for grounding purposes, BCC no violations shall be retained, Note: partial corrections until rest of equipment opened up
|
ELE06-02477
| Final | 8/25/2006 | 8/25/2006 | 8/25/2006 9:02:28 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/25/2006 at 5:28:09 AM. Contact: ###-####. ok to final
|
ELE06-01187
| Electrical Rough-In | 8/24/2006 | 8/25/2006 | 8/25/2006 8:36:02 AM | A | FAIL |
|
|
Area above the lay-in ceiling inspected so ceiling tile may be installed Call John at ###-####; Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, left corr notice, BCC fixtures shall have 2 struct support wires and no low voltage wires shall be on grid. Made corr notice to contr and to owner
|
ELE06-02613
| Electrical Rough-In | 8/24/2006 | 8/25/2006 | 8/25/2006 8:12:53 AM | A | PART |
|
|
this is for the 1st floor, any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford mezzanine walls only ok to cover
|
ELE06-03178
| Electrical Rough-In | 8/24/2006 | 8/25/2006 | 8/25/2006 8:12:01 AM | A | PART |
|
|
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover u/g
|