FIR06-00449
| INSP-Sprinkler Rough-in/Hydro | 8/25/2006 | 8/25/2006 | 8/28/2006 11:21:46 AM | P | PART |
|
|
OH rough-in for a portion of the canopy antifreeze system is good for cover as marked on approved plans, flexible couplings where pipe passes through brick walls at two locations to be installed and verified at next inspection, plywood obstruction in the truss web to be removed per general contractor.
|
FIR06-00337
| INSP-Final Inspection | 8/25/2006 | 8/25/2006 | 8/25/2006 3:24:03 PM | P | PASS |
|
|
Remainder of fire sprinkler work passed inspection.
|
FIR06-00501
| INSP-Final Inspection | 8/25/2006 | 8/25/2006 | 8/25/2006 3:23:10 PM | P | PASS |
|
|
Fire sprinkler work is acceptable, permit finaled.
|
BLD06-01389
| FIRE-Final Inspection | 8/24/2006 | 8/25/2006 | 8/25/2006 1:01:18 PM | A | PASS |
|
|
Life safety inspection passed.
|
FIR06-00237
| INSP-Final Inspection | 8/24/2006 | 8/25/2006 | 8/25/2006 12:35:09 PM | A | PASS |
|
|
Fire alarm work is satisfactory, inspection passed. Sign at the door to FACP room to be posted today per agreement and verified at life safety final.
|
FIR05-00404
| INSP-Final Inspection | 8/24/2006 | 8/25/2006 | 8/25/2006 12:32:45 PM | A | PASS |
|
|
Fire sprinkler final inspection is satisfactory, one missing escutcheon replaced while on site.
|
FIR06-00489
| INSP-Final Inspection | 8/24/2006 | 8/25/2006 | 8/25/2006 11:28:05 AM | A | NR |
|
|
Per phone call from contractor the project is not ready for inspection due to intermittent ground faults, to be rescheduled.
|
FIR06-00557
| INSP-Final Inspection | 8/24/2006 | 8/25/2006 | 8/25/2006 11:26:53 AM | A | FAIL |
|
|
Both manual pull stations are installed above max. height allowed AFF, the H/S and manual pulls installed do not match submittals (different manufacturers).
|