Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00429 INSP-Sprinkler Rough-in/Hydro8/25/20088/25/20088/25/2008 4:48:37 PMPPART
OH inspection for the court area mains and branchlines only completed today-the lower mezzanine piping is not yet installed, noted one missing EQ brace at the NW corner-location circled on plans, noted high temp. heads in place at the vicinity of the unit heaters, riser is not built.
FIR08-00473 INSP-Final Inspection8/25/20088/25/20088/25/2008 4:41:52 PMPPASS
C/N items from last inspection are complete, fire sprinkler permit finaled.
BLD08-01094 FIRE-Final Inspection8/22/20088/25/20088/25/2008 1:42:32 PMPPASS
Fire life safety finaled.
FIR08-00498 INSP-Final Inspection8/25/20088/25/20088/25/2008 1:42:07 PMPPASS
Corrections verified for compliance, fire sprinkler permit okay for final as uprights at the plan mod. area are installed.
FIR08-00388 INSP-Sprinkler Rough-in8/22/20088/25/20088/25/2008 1:06:19 PMAFAIL
SW heads at the sign tower antifreeze loop are overspaced and below max. listed distance from the ceiling, noted several missing retaining straps at numerous locations including mains and branch lines-somel installed while on site, combustibles above the restrooms must be removed or protection provided, waiting area drops are 3/4"-plan shows 1/2" heads, four upright heads at the stock room are obstructed by beams or exceed min. spacing.
BLD07-03063 FIRE-Final Inspection8/22/20088/25/20088/25/2008 11:37:43 AMAPASS
Three exit signs repaired while on site, contractor to replace the fire extinguisher with one tagged/certified extinguisher per discussion and code review notes, remainder of life safety items tested okay, inspection passed.
FIR07-00905 INSP-Final Inspection8/25/20088/25/20088/25/2008 11:34:46 AMAPASS
Verified corrections, seismic clearance provided, fire supply line flush completed, UG permit finaled.
FIR07-00905 INSP-Supply line flush8/22/20088/25/20088/25/2008 11:32:45 AMAPART
UG fire supply line flush completed okay.