ESC09-00397
| General Inspection | 8/25/2009 | 8/25/2009 | 8/25/2009 4:00:08 PM | P | PASS |
|
|
looked ok
|
ESC09-00503
| General Inspection | 8/25/2009 | 8/25/2009 | 8/25/2009 3:59:11 PM | P | PASS |
|
|
looked ok
|
ESC09-00523
| General Inspection | 8/25/2009 | 8/25/2009 | 8/25/2009 3:56:57 PM | P | DONE |
|
|
too early, no sign up, or work started
|
ESC09-00467
| General Inspection | 8/25/2009 | 8/25/2009 | 8/25/2009 3:50:01 PM | P | DONE |
|
|
too early, no sign or work started
|
ESC09-00468
| General Inspection | 8/25/2009 | 8/25/2009 | 8/25/2009 3:28:28 PM | P | NR |
|
|
too early, no signs or work started
|
ELE09-01581
| Final | 8/25/2009 | 8/25/2009 | 8/25/2009 3:00:00 PM | P | PASS |
|
|
Street flasher 2 Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok to final, no esc this project
|
ELE09-01527
| Temporary Service | 8/24/2009 | 8/25/2009 | 8/25/2009 2:58:40 PM | A | PASS |
|
|
Dennis Phone #: ###-#### t/s o/h n ok, no esc this project, NOTE: power already swung to pole and energized
|
ELE09-01580
| Final | 8/25/2009 | 8/25/2009 | 8/25/2009 2:11:25 PM | P | PASS |
|
|
Street Flasher 1 Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok to final
|
ELE09-00928
| Final | 8/25/2009 | 8/25/2009 | 8/25/2009 1:41:21 PM | P | CANC |
|
|
Please provide electrical final. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean called contractor, he asked for am inspection, not pm, they will recall, no esc this project
|
ELE09-01581
| Permanent Service | 8/25/2009 | 8/25/2009 | 8/25/2009 1:11:10 PM | P | PASS |
|
|
Street flasher 2 Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson p/s o/h n ok, no esc this project
|
ELE09-01580
| Permanent Service | 8/25/2009 | 8/25/2009 | 8/25/2009 1:09:20 PM | P | PASS |
|
|
Street Flasher 1 Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson p/s o/h n ok, no esc this project
|
ELE09-01537
| Final | 8/25/2009 | 8/25/2009 | 8/25/2009 1:06:38 PM | P | PASS |
|
|
or ###-#### Phone #: ###-#### called, ok to final, no esc this project
|
ELE09-01565
| Temporary Service | 8/24/2009 | 8/25/2009 | 8/25/2009 11:32:44 AM | A | FAIL |
|
|
Brandon Phone #: ###-#### called, left correction notice, NEC 250.24(B) shall provide unspliced main bonding jumper to connect the equipment grounding conductor and the service disconnect enclosure to the grounded conductor per 250.28, 406.8(B) 15 and 20 amp receptacles shall be listed weather resistant type, fee due
|
ELE09-01566
| Temporary Service | 8/24/2009 | 8/25/2009 | 8/25/2009 11:28:14 AM | A | FAIL |
|
|
Brandon Phone #: ###-#### called, left correction notice, NEC 250.24(B) shall provide unspliced main bonding jumper to connect the equipment grounding conductor and the service disconnect enclosure to the grounded conductor per 250.28, 406.8(B) 15 and 20 amp receptacles shall be listed weather resistant type, fee due
|
ELE09-01563
| Temporary Service | 8/24/2009 | 8/25/2009 | 8/25/2009 11:27:23 AM | A | FAIL |
|
|
Brandon Phone #: ###-#### called, left correction notice NEC 250.24(B) shall provide unspliced main bonding jumper to connect the equipment grounding conductor and the service disconnect enclosure to the grounded conductor per 250.28, 406.8(B) 15 and 20 amp receptacles shall be listed weather resistant type, fee due
|
ELE09-01142
| Final | 8/24/2009 | 8/25/2009 | 8/25/2009 10:24:05 AM | A | PASS |
|
|
Dave Jackson Phone #: ###-#### called contractor, ok to final, no esc this project
|
ELE09-01567
| Final | 8/24/2009 | 8/25/2009 | 8/25/2009 10:01:51 AM | A | CANC |
|
|
Vern Phone #: ###-####- call 30 mins prior to going to meet see conference
|
ELE09-01567
| Conference | 8/25/2009 | 8/25/2009 | 8/25/2009 10:01:19 AM | A | DONE |
|
|
Vern Phone #: ###-####- call 30 mins prior to going to meet met contractor, told that equipment shall be listed, schedule inspection when plant down, check available short circuit availability with ipco, find out about fiels evaluations, and area classification, no esc this project
|
ELE09-01572
| Temporary Service | 8/24/2009 | 8/25/2009 | 8/25/2009 8:52:28 AM | A | PASS |
|
|
Mike Phone #: ###-#### calle4d contractor, left message, t/s u/g n ok
|
ELE09-01457
| Electrical Rough-In | 8/24/2009 | 8/25/2009 | 8/25/2009 8:33:17 AM | A | FAIL |
|
|
Allen--conduit for pool Phone #: ###-#### called, left correction notice, NEC 300.5 minimum burial depth shall be 18" except under 4" concrete, 352.36 there shall not more than 360 degrees total bends in raceway, shall use schedule 80 where subject to physical damage
|