Inspections for the day of: Tuesday, August 25, 2009.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC09-00397 General Inspection8/25/20098/25/20098/25/2009 4:00:08 PMPPASS
looked ok
ESC09-00503 General Inspection8/25/20098/25/20098/25/2009 3:59:11 PMPPASS
looked ok
ESC09-00523 General Inspection8/25/20098/25/20098/25/2009 3:56:57 PMPDONE
too early, no sign up, or work started
ESC09-00467 General Inspection8/25/20098/25/20098/25/2009 3:50:01 PMPDONE
too early, no sign or work started
ESC09-00468 General Inspection8/25/20098/25/20098/25/2009 3:28:28 PMPNR
too early, no signs or work started
ELE09-01581 Final8/25/20098/25/20098/25/2009 3:00:00 PMPPASS
Street flasher 2 Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok to final, no esc this project
ELE09-01527 Temporary Service8/24/20098/25/20098/25/2009 2:58:40 PMAPASS
Dennis Phone #: ###-#### t/s o/h n ok, no esc this project, NOTE: power already swung to pole and energized
ELE09-01580 Final8/25/20098/25/20098/25/2009 2:11:25 PMPPASS
Street Flasher 1 Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok to final
ELE09-00928 Final8/25/20098/25/20098/25/2009 1:41:21 PMPCANC
Please provide electrical final. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean called contractor, he asked for am inspection, not pm, they will recall, no esc this project
ELE09-01581 Permanent Service8/25/20098/25/20098/25/2009 1:11:10 PMPPASS
Street flasher 2 Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson p/s o/h n ok, no esc this project
ELE09-01580 Permanent Service8/25/20098/25/20098/25/2009 1:09:20 PMPPASS
Street Flasher 1 Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson p/s o/h n ok, no esc this project
ELE09-01537 Final8/25/20098/25/20098/25/2009 1:06:38 PMPPASS
or ###-#### Phone #: ###-#### called, ok to final, no esc this project
ELE09-01565 Temporary Service8/24/20098/25/20098/25/2009 11:32:44 AMAFAIL
Brandon Phone #: ###-#### called, left correction notice, NEC 250.24(B) shall provide unspliced main bonding jumper to connect the equipment grounding conductor and the service disconnect enclosure to the grounded conductor per 250.28, 406.8(B) 15 and 20 amp receptacles shall be listed weather resistant type, fee due
ELE09-01566 Temporary Service8/24/20098/25/20098/25/2009 11:28:14 AMAFAIL
Brandon Phone #: ###-#### called, left correction notice, NEC 250.24(B) shall provide unspliced main bonding jumper to connect the equipment grounding conductor and the service disconnect enclosure to the grounded conductor per 250.28, 406.8(B) 15 and 20 amp receptacles shall be listed weather resistant type, fee due
ELE09-01563 Temporary Service8/24/20098/25/20098/25/2009 11:27:23 AMAFAIL
Brandon Phone #: ###-#### called, left correction notice NEC 250.24(B) shall provide unspliced main bonding jumper to connect the equipment grounding conductor and the service disconnect enclosure to the grounded conductor per 250.28, 406.8(B) 15 and 20 amp receptacles shall be listed weather resistant type, fee due
ELE09-01142 Final8/24/20098/25/20098/25/2009 10:24:05 AMAPASS
Dave Jackson Phone #: ###-#### called contractor, ok to final, no esc this project
ELE09-01567 Final8/24/20098/25/20098/25/2009 10:01:51 AMACANC
Vern Phone #: ###-####- call 30 mins prior to going to meet see conference
ELE09-01567 Conference8/25/20098/25/20098/25/2009 10:01:19 AMADONE
Vern Phone #: ###-####- call 30 mins prior to going to meet met contractor, told that equipment shall be listed, schedule inspection when plant down, check available short circuit availability with ipco, find out about fiels evaluations, and area classification, no esc this project
ELE09-01572 Temporary Service8/24/20098/25/20098/25/2009 8:52:28 AMAPASS
Mike Phone #: ###-#### calle4d contractor, left message, t/s u/g n ok
ELE09-01457 Electrical Rough-In8/24/20098/25/20098/25/2009 8:33:17 AMAFAIL
Allen--conduit for pool Phone #: ###-#### called, left correction notice, NEC 300.5 minimum burial depth shall be 18" except under 4" concrete, 352.36 there shall not more than 360 degrees total bends in raceway, shall use schedule 80 where subject to physical damage