FIR09-00290
| INSP-Final Inspection | 8/24/2009 | 8/25/2009 | 8/28/2009 4:14:48 PM | A | CANC |
|
|
Inspection request precluded by work on FIR09-00296 dated 8/25.
|
FIR09-00033
| INSP-Sprinkler Rough-in/Hydro | 8/25/2009 | 8/25/2009 | 8/28/2009 1:06:18 PM | P | DONE |
|
|
Duplicate inspection request-see activity notes for details.
|
FIR09-00033
| INSP-Sprinkler Rough-in | 8/21/2009 | 8/25/2009 | 8/28/2009 1:04:54 PM | A | FAIL |
|
|
See C/N on site for inspection comments completed 8/26 by T. Frost--System 13 had an HVAC duct blocking the sprinklers at column line C. System 11 needs sprinklers in the doorway areas. System 14 Ceiling tile missing through out. In the scan department of system 14 there cannot be storage on the top level of the racks. City of Boise still has not received a letter from Peerless Pump on the malfunctioning PLD. System 21 condensate piping is blocking a sprinkler head. All dry storage systems. The 4x4 structural tubing has not been removed and the ESFR sprinklers are blocked.
|
FIR09-00033
| INSP-Alarm Testing | 8/21/2009 | 8/25/2009 | 8/25/2009 1:50:32 PM | P | FAIL |
|
|
Alarm Testing for preaction activation. Phone #: ###-#### Internet Inspection Request from: Jeff Packham ATTN: See notes for FIR09-00296--Deficient items found during the first three hours of inspection include missing NFPA 72 Record of Inspection and Testing with a copy of supervising station signals report per plan review note #3, missing signage per review note #1, provide a lock and label at the power circut breaker to the panel, A/C power off failed to report to the main FACP-see note #5, per details on approved plans 90 deg. ells to be avoided and 6" to 10" clearance to be provided at each side of the freezer wall to avoid ice plugs-noted significant frosting at these locations, the first VESDA fault at system 28 did not report, plans incorrectly show location of system 27, south line of smoke detection at systems 16,17, and 18 are overspaced-see fire code review note #13, provide a building map at the releasing panel indicating floorplan layout and locations of all initiating devices-see plan review note #15, repairs underway at VESDA system 29.
|
FIR09-00296
| INSP-Final Inspection | 8/24/2009 | 8/25/2009 | 8/25/2009 1:47:52 PM | A | FAIL |
|
|
Deficient items found during the first three hours of inspection include missing NFPA 72 Record of Inspection and Testing with a copy of supervising station signals report per plan review note #3, missing signage per review note #1, provide a lock and label at the power circut breaker to the panel, A/C power off failed to report to the main FACP-see note #5, per details on approved plans 90 deg. ells to be avoided and 6" to 10" clearance to be provided at each side of the freezer wall to avoid ice plugs-noted significant frosting at these locations, the first VESDA fault at system 28 did not report, plans incorrectly show location of system 27, south line of smoke detection at systems 16,17, and 18 are overspaced-see fire code review note #13, provide a building map at the releasing panel indicating floorplan layout and locations of all initiating devices-see plan review note #15, repairs underway at VESDA system 29.
|
FIR09-00033
| INSP-Alarm Testing | 8/21/2009 | 8/25/2009 | 8/24/2009 12:58:48 PM | A | NR |
|
|
Pending FIR09-00296
|