BLD10-01491
| FIRE-Sprinkler Rough-in | 8/25/2010 | 8/25/2010 | 8/26/2010 4:40:16 PM | P | PART |
|
|
Okayed overhead fire sprinkler system modifications for cover at the drop ceilings.
|
FIR10-00054
| INSP-Sprinkler Rough-in/Hydro | 8/25/2010 | 8/25/2010 | 8/26/2010 4:39:08 PM | P | PART |
|
|
Concluded satisfactory pneumatic test of the new preaction system with no pressure loss at the guage.
|
FIR10-00368
| INSP-Final Inspection | 8/24/2010 | 8/25/2010 | 8/26/2010 4:38:10 PM | A | PASS |
|
|
Scope of fire alarm work passed inspection. Permit finaled.
|
FIR10-00221
| FIR-Aging Inspection | 8/25/2010 | 8/25/2010 | 8/25/2010 12:58:57 PM | | DONE |
|
|
Site visit revealed work has been completed. However, lacking plans and access to all areas for verification of code compliance. Need inspection request by contractor for permit final.
|
BLD10-01335
| FIRE-Final Inspection | 8/24/2010 | 8/25/2010 | 8/25/2010 12:56:12 PM | A | PASS |
|
|
Noted correction items field verified for completion. Fire life safety finaled.
|
FIR10-00372
| INSP-Final Inspection | 8/24/2010 | 8/25/2010 | 8/25/2010 12:54:59 PM | A | PASS |
|
|
Fire sprinkler permit passed final walkthrough, one remaining tile at a pendent head installed while on site. Permit finaled.
|
BLD10-01337
| FIRE-Final Inspection | 8/24/2010 | 8/25/2010 | 8/25/2010 12:53:22 PM | A | FAIL |
|
|
Project related fire alarm permit must be issued and requested for final inspection prior to building fire life safety approval. Also need to provide and post one fire extinguisher per plan, replace door closures, access ramps are not yet finished.
|
BLD10-01336
| FIRE-Final Inspection | 8/24/2010 | 8/25/2010 | 8/25/2010 12:52:49 PM | A | FAIL |
|
|
Project related fire alarm permit must be issued and requested for final inspection prior to building fire life safety approval. Also need to provide and post one fire extinguisher per plan, replace door closures, access ramps are not yet finished.
|