BLD10-01869
| FIRE-Final Inspection | 8/24/2010 | 8/25/2010 | 8/26/2010 11:18:09 AM | P | PASS |
|
|
Life safety passed
|
BLD10-01997
| FIRE-Final Inspection | 8/25/2010 | 8/25/2010 | 8/25/2010 3:26:06 PM | P | FAIL |
|
|
Sprinkler pendants are over spaced in two locations. I have spoken to Jeff with Treasure Valley Fire about the specific locations. Also all of the exit signs and emergency lights need to be repaired.
|
FIR10-00072
| INSP-Sprinkler Rough-in | 8/25/2010 | 8/25/2010 | 8/25/2010 3:11:27 PM | P | PASS |
|
|
The sprinkler piping in the high ceiling area, as discussed, can be covered.
|
FIR10-00286
| INSP-Sprinkler Rough-in | 8/25/2010 | 8/25/2010 | 8/25/2010 2:55:54 PM | P | CANC |
|
|
Cancelled due to time constraints. I spoke to Jeremy about meeting tomorrow morning.
|
FIR10-00028
| INSP-Sprinkler Rough-in | 8/25/2010 | 8/25/2010 | 8/25/2010 2:50:33 PM | P | PASS |
|
|
Above ground hydro test passed.
|
FIR10-00413
| INSP-Final Inspection | 8/24/2010 | 8/25/2010 | 8/25/2010 1:59:36 PM | P | PASS |
|
|
Permit finaled
|
FIR10-00369
| INSP-Sprinkler Rough-in/Hydro | 8/25/2010 | 8/25/2010 | 8/25/2010 1:59:06 PM | P | PASS |
|
|
Rough-in passed. Sprinkler piping can be covered.
|
FIR10-00199
| INSP-Final Inspection | 8/25/2010 | 8/25/2010 | 8/25/2010 1:56:18 PM | P | PASS |
|
|
Permit finaled
|
BLD10-00114
| FIRE-Supply Line Cover | 8/25/2010 | 8/25/2010 | 8/25/2010 1:49:48 PM | A | CANC |
|
|
This inspection is for a sprinkler cover. No entry is being made under this building permit. The entry will be made under the correct fire sprinkler permit.
|
FIR10-00413
| INSP-Sprinkler Rough-in | 8/24/2010 | 8/25/2010 | 8/25/2010 1:16:23 PM | A | PASS |
|
|
Sprinkler piping is ok to cover.
|
FIR10-00028
| INSP-Sprinkler Rough-in/Hydro | 8/24/2010 | 8/25/2010 | 8/25/2010 12:56:10 PM | A | FAIL |
|
|
Above ground hydro test failed. Earthquaking has been corrected and the FDC piping has been installed. Phone #: ###-####
|
FIR10-00336
| INSP-Final Inspection | 8/25/2010 | 8/25/2010 | 8/25/2010 12:43:34 PM | P | CANC |
|
|
Per Chris Farnsworth the hvac units were not shutting down upon activation of the duct smoke detectors. Inspection to be rescheduled for tomorrow morning.
|
FIR10-00036
| INSP-Final Inspection | 8/19/2010 | 8/25/2010 | 8/25/2010 12:05:28 PM | A | CANC |
|
|
Simplex called an inspection for this permit number by mistake.
|
FIR10-00322
| INSP-Final Inspection | 8/25/2010 | 8/25/2010 | 8/25/2010 11:32:47 AM | P | CANC |
|
|
To be rescheduled for tomorrow when the fire alarm contractor is ready.
|