Inspections for the day of: Wednesday, August 25, 2010.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-01869 FIRE-Final Inspection8/24/20108/25/20108/26/2010 11:18:09 AMPPASS
Life safety passed
BLD10-01997 FIRE-Final Inspection8/25/20108/25/20108/25/2010 3:26:06 PMPFAIL
Sprinkler pendants are over spaced in two locations. I have spoken to Jeff with Treasure Valley Fire about the specific locations. Also all of the exit signs and emergency lights need to be repaired.
FIR10-00072 INSP-Sprinkler Rough-in8/25/20108/25/20108/25/2010 3:11:27 PMPPASS
The sprinkler piping in the high ceiling area, as discussed, can be covered.
FIR10-00286 INSP-Sprinkler Rough-in8/25/20108/25/20108/25/2010 2:55:54 PMPCANC
Cancelled due to time constraints. I spoke to Jeremy about meeting tomorrow morning.
FIR10-00028 INSP-Sprinkler Rough-in8/25/20108/25/20108/25/2010 2:50:33 PMPPASS
Above ground hydro test passed.
FIR10-00413 INSP-Final Inspection8/24/20108/25/20108/25/2010 1:59:36 PMPPASS
Permit finaled
FIR10-00369 INSP-Sprinkler Rough-in/Hydro8/25/20108/25/20108/25/2010 1:59:06 PMPPASS
Rough-in passed. Sprinkler piping can be covered.
FIR10-00199 INSP-Final Inspection8/25/20108/25/20108/25/2010 1:56:18 PMPPASS
Permit finaled
BLD10-00114 FIRE-Supply Line Cover8/25/20108/25/20108/25/2010 1:49:48 PMACANC
This inspection is for a sprinkler cover. No entry is being made under this building permit. The entry will be made under the correct fire sprinkler permit.
FIR10-00413 INSP-Sprinkler Rough-in8/24/20108/25/20108/25/2010 1:16:23 PMAPASS
Sprinkler piping is ok to cover.
FIR10-00028 INSP-Sprinkler Rough-in/Hydro8/24/20108/25/20108/25/2010 12:56:10 PMAFAIL
Above ground hydro test failed. Earthquaking has been corrected and the FDC piping has been installed. Phone #: ###-####
FIR10-00336 INSP-Final Inspection8/25/20108/25/20108/25/2010 12:43:34 PMPCANC
Per Chris Farnsworth the hvac units were not shutting down upon activation of the duct smoke detectors. Inspection to be rescheduled for tomorrow morning.
FIR10-00036 INSP-Final Inspection8/19/20108/25/20108/25/2010 12:05:28 PMACANC
Simplex called an inspection for this permit number by mistake.
FIR10-00322 INSP-Final Inspection8/25/20108/25/20108/25/2010 11:32:47 AMPCANC
To be rescheduled for tomorrow when the fire alarm contractor is ready.