Inspections for the day of: Thursday, August 25, 2011.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00467 INSP-Final Inspection8/25/20118/25/20118/25/2011 4:01:35 PMPPASS
Reinspection for the scope of work passed.
FIR11-00355 INSP-Sprinkler Rough-in8/25/20118/25/20118/25/2011 4:00:36 PMPPART
Verified corrections at the administration area and kindergarden classroom, okay to sheetrock the deck only at classrooms 113 and 115. Discussed possible obstruction issues at the soffit in rooms 113 and 115.
BLD11-00811 FIRE-Final Inspection8/25/20118/25/20118/25/2011 3:57:41 PMPFAIL
Noted items include; signage at the main entry/exit, remove manual thumbturn at the second exit, provide approved hardware at the restroom door, post fire extinguishers as discussed.
FIR10-00540 INSP-Final Inspection8/25/20118/25/20118/25/2011 3:55:52 PMPPASS
C/N items field verified for completion. Fire sprinkler permit approved for final.
BLD11-01939 FIRE-Final Inspection8/24/20118/25/20118/25/2011 3:54:03 PMAPASS
Fire life safety final passed pending installation of approved hardware at the second exit door per plan review comments. Structural inspector to verify prior to final.
FIR11-00369 INSP-Final Inspection8/24/20118/25/20118/25/2011 3:51:58 PMAPASS
Scope of fire sprinkler permit work finaled.
FIR11-00369 INSP-Sprinkler Rough-in/Hydro8/25/20118/25/20118/25/2011 3:50:58 PMPCANC
OH rough-in approved for cover.