ELE13-01672
| ELE-Aging Inspection | 8/25/2015 | 8/25/2015 | 8/26/2015 2:49:11 PM | | DONE |
|
|
Eric said he will call for final
|
ELE15-02131
| Final | 8/25/2015 | 8/25/2015 | 8/25/2015 2:57:30 PM | P | PART |
|
|
Units east wing 5th floor. Phone #: ###-#### Inspection requested via web by Rafael Castillo final 100% except corridors
|
ELE15-02132
| Final | 8/24/2015 | 8/25/2015 | 8/25/2015 2:55:42 PM | A | PART |
|
|
Unit inspections, 5th floor west wing. Phone #: ###-#### Inspection requested via web by Rafael Castillo final 100% except rm 540 and corridors
|
ELE15-01867
| Electrical Rough-In | 8/25/2015 | 8/25/2015 | 8/25/2015 12:12:41 PM | P | PASS |
|
|
Contact: Ryan Garrett - Temp Occupancy inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden temp. occupancy only OK
|
ELE15-02327
| Final | 8/24/2015 | 8/25/2015 | 8/25/2015 11:33:45 AM | A | PASS |
|
|
For access please call Ed 1/2 hr prior to inspection. ###-#### Inspection requested via web by Terry Scott final ok
|
ELE15-01657
| Final | 8/24/2015 | 8/25/2015 | 8/25/2015 11:18:11 AM | A | NH |
|
|
Jerome Ferlitch is contact. ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce no response to 2 calls to find work location at airport
|
ELE15-01617
| Conference | 8/24/2015 | 8/25/2015 | 8/25/2015 10:40:51 AM | A | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton discuss clearances for electrical panels in air handelers as per 110.26(A)(1). Need 3' 6" for the 277 voltage in front of units and approx. 30" wide clearance. Exceptions for side panels to replace filters and blower motors where limited.
|
ELE12-01968
| Final | 8/25/2015 | 8/25/2015 | 8/25/2015 9:46:45 AM | P | PASS |
|
|
Please call 1hr ahead coming from Star, Brian Phone #: ###-#### or Mitch ###-#### final ok
|
ELE15-02679
| Electrical Rough-In | 8/24/2015 | 8/25/2015 | 8/25/2015 9:31:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl r/i ok
|
GCE15-00105
| GCE-Final | 8/24/2015 | 8/25/2015 | 8/25/2015 8:53:20 AM | A | PASS |
|
|
David ###-#### final ok
|
ELE15-02613
| Final | 8/24/2015 | 8/25/2015 | 8/25/2015 8:18:50 AM | P | PART |
|
|
Inspection requested via web by Clint Tate corrections made emergency exits and lights still being installed temporary. occupancy ok
|