Inspections for the day of: Thursday, August 25, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorAlan Hauser
TitleMEC-COM/RES INSPECTOR
Phone #794-9453
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC16-02965 Final8/25/20168/25/20168/25/2016 4:37:29 PMPPASS
MEC16-03762 Final8/25/20168/25/20168/25/2016 3:56:26 PMPFAIL
80% furnace accessed from a bedroom, need all outside combustion air and self closing door that is sealed.
MEC16-03839 Final8/25/20168/25/20168/25/2016 3:30:44 PMPPASS
MEC16-03679 Final8/23/20168/25/20168/25/2016 3:23:09 PMPPASS
MEC16-03544 Pressure Test8/25/20168/25/20168/25/2016 2:56:04 PMPPASS
20#, 5# on furn. and w/h flues
MEC16-03544 Rough-in8/25/20168/25/20168/25/2016 2:54:12 PMPPART
hvac ok, still need fresh air to return
MEC16-03818 Rough-in8/25/20168/25/20168/25/2016 2:29:58 PMPPASS
MEC16-03834 Final8/23/20168/25/20168/25/2016 2:04:45 PMPPASS
MEC16-03638 Final8/18/20168/25/20168/25/2016 1:37:16 PMPPASS
MEC16-03521 Rough-in8/24/20168/25/20168/25/2016 11:32:53 AMAPASS
MEC16-03833 Rough-in8/24/20168/25/20168/25/2016 11:32:37 AMAFAIL
framing above f/p doesn't meet table 10.2, as per manufacture
MEC16-03866 Rough-in8/24/20168/25/20168/25/2016 10:45:32 AMAPART
20# test ok on new piping in new addition only. There will be more piping later.
MEC16-02118 Final8/24/20168/25/20168/25/2016 10:12:03 AMAPASS
MEC16-03451 Rough-in8/24/20168/25/20168/25/2016 10:04:31 AMAPASS
MEC15-02333 Mec-Aging Inspection8/25/20168/25/20168/25/2016 8:50:06 AM CANC