Inspections for the day of: Thursday, August 25, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00808 INSP-Sprinkler Rough-in/Hydro8/25/20168/25/20168/25/2016 2:47:49 PMPDONE
Hydrostatic test for overhead fire sprinkler piping complete.
FIR15-00727 INSP-Sprinkler Rough-in8/25/20168/25/20168/25/2016 2:15:18 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in the ballroom, sections B and C complete. Overhead fire sprinkler piping located above the grid ceiling in ballroom approved for cover.
FIR16-00314 INSP-Sprinkler Rough-in/Hydro8/24/20168/25/20168/25/2016 12:17:50 PMAPASS
Rough to cover inspection for overhead fire sprinkler piping on level 1 complete, level 1 overhead fire sprinkler piping approved for cover. Hydrostatic test for overhead fire sprinkler throughout building complete.
FIR16-00101 INSP-Sprinkler Rough-in/Hydro8/24/20168/25/20168/25/2016 11:58:19 AMAFAIL
Overhead fire sprinkler piping located in attic spaces on level 5 not approved for cover, plastic sheeting is installed over fire sprinkler piping but no insulation has been installed above piping, insulation tenting needs to installed over the fire sprinkler piping and inspected before cover of overhead fire sprinkler piping in attic spaces is approved.
BLD16-02360 FIRE-Final Inspection8/24/20168/25/20168/25/2016 11:18:23 AMAPASS
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher is in common area with a current i nspection tag. Final life fire safety inspection passed/complete.
FIR16-00526 INSP-Final Inspection8/25/20168/25/20168/25/2016 11:17:01 AMPPASS
Final fire sprinkler inspection passed/complete
FIR16-00526 INSP-Sprinkler Rough-in8/25/20168/25/20168/25/2016 11:16:00 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping located in area of work complete, overhead fire sprinkler piping in area of work approved for cover.
FIR16-00305 INSP-Sprinkler Rough-in8/24/20168/25/20168/25/2016 11:04:21 AMAPASS
Partial rough to cover inspection complete for overhead fire sprinkler piping on levels 2, 3 and 4. Notated the city approved drawings with green highlighter overhead fire sprinkler piping approved for cover.
FIR16-00292 INSP-Final Inspection8/22/20168/25/20168/25/2016 10:20:34 AMAPASS
Final fire alarm communicator inspection passed/complete.
FIR15-00641 INSP-Sprinkler Rough-in8/24/20168/25/20168/25/2016 10:01:18 AMAPASS
Rough to cover inspection for hardlids located on level 5 annex complete, overhead fire sprinkler piping located above hardlids approved for cover.
FIR16-00146 INSP-Sprinkler Rough-in8/24/20168/25/20168/25/2016 9:59:44 AMAPASS
Rough to cover inspection for level 9and stairwells overhead fire sprinkler piping compete, overhead fire sprinkler piping located on level 9 and stairwells approved for cover.