ELE02-02539
| Final | 8/20/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 08/20/2002 at 10:40:43. Contact: ###-####.
grounding of panel and upstairs recep. 8/26/2002 1:26:07 PM
|
ELE01-02215
| Final | 8/22/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | A | FAIL |
|
|
###-#### HAROLD
closet light location and improper use of cords 8/26/2002 1:23:48 PM
|
ELE02-00766
| Final | 8/23/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | A | PASS |
|
|
###-####
|
ELE01-00245
| Electrical Rough-In | 8/25/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 08/25/2002 at 21:14:46. Contact: ###-####.
Had conf under sized ground, 6 in. free conductor , Box fill, and protection of romex. 8/26/2002 1:28:06 PM
|
ELE02-02641
| Rough-In Permanent Service | 8/26/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | P | FAIL |
|
|
###-#### mitch
250.148 box fill, location of receps and screws inside NM box 8/26/2002 4:43:58 PM
|
ELE02-02176
| Final | 8/26/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | P | FAIL |
|
|
###-####
Line to Load reversed on outside recep. 8/26/2002 3:46:36 PM
|
ELE01-03949
| Rough-In Permanent Service | 8/26/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 08/26/2002 at 10:51:08. Contact: ###-####. Equipment grounding conductor not in terminal properly, neutral in sub panel not isolated, and undersized grounding electrode conductor. 8/26/2002 2:28:31 PM
|