Inspections for the day of: Monday, August 26, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD01-02182 FIRE-Final Inspection8/22/20028/26/20028/26/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 08/22/2002 at 16:36:19. Contact: ###-####. need detectors for AHU shutdown; keyed lock on security door; mags on front door - need to clarify operation or comply with plan review notes; fire lane markings; address 8/26/2002 12:48:53 PM
BLD02-01750 FIRE-Final Inspection8/26/20028/26/20028/26/2002 12:00:00 AMPFAIL
this permit is for a B occupancy; when I arrived I found the room filled with elementary school type desks and chairs; there were two teachers and they said the space was for a new classroom; I called Jason Blais and he said that the architect was to submit plans for the schoolroom; called Jim Storey and he said he would contact the GC about the problem; 8/26/2002 1:40:55 PM
FIR02-00339 INSP-Final Inspection8/26/20028/26/20028/26/2002 12:00:00 AMPFAIL
###-#### construction type is obstructed combustible - head spacing to be 168 sq ft; will need to verify spacing; per Bill Alexander they won't need to resubmit but to verify spacing; need spare heads 8/26/2002 4:32:30 PM
BLD02-01263 FIRE-Conference8/26/20028/26/20028/26/2002 12:00:00 AMPPART
met with GC while doing the fire sprinkler r/i; door hardware per plans; exit signs per plans; need fire alarm plans for new duct detectors