BLD01-02182
| FIRE-Final Inspection | 8/22/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 08/22/2002 at 16:36:19. Contact: ###-####. need detectors for AHU shutdown; keyed lock on security door; mags on front door - need to clarify operation or comply with plan review notes; fire lane markings; address 8/26/2002 12:48:53 PM
|
BLD02-01750
| FIRE-Final Inspection | 8/26/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | P | FAIL |
|
|
this permit is for a B occupancy; when I arrived I found the room filled with elementary school type desks and chairs; there were two teachers and they said the space was for a new classroom; I called Jason Blais and he said that the architect was to submit plans for the schoolroom; called Jim Storey and he said he would contact the GC about the problem; 8/26/2002 1:40:55 PM
|
FIR02-00339
| INSP-Final Inspection | 8/26/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | P | FAIL |
|
|
###-#### construction type is obstructed combustible - head spacing to be 168 sq ft; will need to verify spacing; per Bill Alexander they won't need to resubmit but to verify spacing; need spare heads 8/26/2002 4:32:30 PM
|
BLD02-01263
| FIRE-Conference | 8/26/2002 | 8/26/2002 | 8/26/2002 12:00:00 AM | P | PART |
|
|
met with GC while doing the fire sprinkler r/i; door hardware per plans; exit signs per plans; need fire alarm plans for new duct detectors
|