FIR04-00300
| INSP-Sprinkler Rough-in/Hydro | 8/25/2004 | 8/26/2004 | 8/26/2004 12:00:00 AM | A | PASS |
|
|
200 lbs hydro test has passed. Started the 24 hour air test at 3:00 with 48psi on the gauge 8/26/2004 3:21:26 PM
|
FIR04-00236
| INSP-Sprinkler Rough-in | 8/25/2004 | 8/26/2004 | 8/26/2004 12:00:00 AM | A | PASS |
|
|
fire sprinklers are ok to cover. After Bill had a chance to review the submittal provided by the contractor for hanging sprinkler it was found that the cross webbing may not support the sprinkler piping. Contractor to provide verification 8/26/2004 9:10:15 AM
|
BLD01-02249
| BLD-Conference | 8/26/2004 | 8/26/2004 | 8/26/2004 12:00:00 AM | A | DONE |
|
|
I spoke to the ymca rep and went over remaining items for my final.
|
FIR04-00273
| INSP-Final Inspection | 8/26/2004 | 8/26/2004 | 8/26/2004 12:00:00 AM | P | PASS |
|
|
Hood suppression system operated correctly
|
FIR04-00470
| INSP-Sprinkler Rough-in/Hydro | 8/26/2004 | 8/26/2004 | 8/26/2004 12:00:00 AM | P | PASS |
|
|
sprinkler piping is ok to cover 8/26/2004 2:08:35 PM
|
BLD03-01974
| FIRE-Final Inspection | 8/26/2004 | 8/26/2004 | 8/26/2004 12:00:00 AM | P | FAIL |
|
|
Inspection was actually a conference with the owner. We went over life/safety requirements which included door hardware, emergency lighting, exit signs, rated doors and smoke seals. Plan reviewer missed the exit discharge lighting so I notified the owner it would be require (plan reviewer verified this), also additional walls have been built in two of the tenant spaces. Per plan reviewer its structurals call on resubmittals 8/26/2004 4:23:58 PM
|
BLD04-01409
| FIRE-Final Inspection | 8/25/2004 | 8/26/2004 | 8/26/2004 12:00:00 AM | P | PASS |
|
|
Fire life/safety finaled. Structural please verify that the tactil exit sign gets mounted 8/26/2004 2:07:38 PM
|
FIR03-00453
| INSP-Final Inspection | 8/25/2004 | 8/26/2004 | 8/26/2004 12:00:00 AM | P | FAIL |
|
|
hvac unit at point 74 did not shutdown. Could not get unit at point 75 to start. Kitchen door does not latch. Flow switch at point 489 did not operate within 90 seconds. Still need to connect hood (point reports), the remaining duct smoke detectors and sprinkler risers and all of the items listed above that didn't work the first time 8/26/2004 3:45:56 PM
|