Inspections for the day of: Friday, August 26, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02841 Temporary Service8/24/20058/26/20058/26/2005 4:22:07 PMPFAIL
Scheduled by a contractor via Hello! on 8/24/2005 at 5:17:48 PM. Contact: ###-####. called contr, left corr notice 250.24 bonding jumper shall be connected between gec and grounded conductor, 250.53(G) ground rod shall be 8' long and flush with or below ground, 312.5 conductors entering enclosure shall have abrasion protection, fee due
ELE05-02824 Temporary Service8/24/20058/26/20058/26/2005 4:18:18 PMPFAIL
Scheduled by a contractor via Hello! on 8/24/2005 at 5:18:42 PM. Contact: ###-####. called contr, left corr notice, fee due. 312.5 conductors entering cnclosure shall have abrasion protection, 110.12(C) there shall be no broken parts, 250.56 supplementary ground rod shall be installed (8'-0" long)
ELE05-03070 Temporary Service8/26/20058/26/20058/26/2005 4:14:52 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Joe Thomas 404.8 center of breaker handle shall be max 6'-7" above floor, 312.5 all conductors entering enclosure shall have abrasion protection,250.92(A) metal parts of service equipment shall be bonded,408.4 circuit directory shall be provided, re-inspection fee due,called contr, left corr notice
ELE05-03125 Electrical Rough-In8/26/20058/26/20058/26/2005 2:30:06 PMPPASS
###-#### ric ok walls and clg, service will do later
ELE05-02200 Final8/26/20058/26/20058/26/2005 2:09:06 PMPPASS
lloyd --call 1st for access ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final
ELE05-02446 Permanent Service8/26/20058/26/20058/26/2005 1:21:22 PMPPASS
Service ready, please contact Julian for service location, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters p/s u/g exst ok
ELE05-02808 Final8/26/20058/26/20058/26/2005 10:35:56 AMANR
Scheduled by a contractor via Hello! on 8/26/2005 at 7:22:55 AM. talked to contr. will recall
ELE05-03116 Permanent Service8/25/20058/26/20058/26/2005 10:33:20 AMAFAIL
###-#### - bill Told owner to drive 2 gnd rods and install at service with #6 copper bare. rest ok
ELE05-03114 Conference8/25/20058/26/20058/26/2005 9:35:57 AMADONE
###-#### - JEAN NOTE: PLEASE 1/2 HR PRIOR TO INSPECTION talked about new service, etc.
ELE05-03112 Electrical Rough-In8/25/20058/26/20058/26/2005 8:47:02 AMAPASS
ANY QUESTIONS PLEASE CALL ED SCHALLOCK; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ric ok. 3 rooms with walls demo and lite sws to 3-way, add few cut-in recpts.
ELE05-02489 Final8/26/20058/26/20058/26/2005 8:19:07 AMAPASS
Scheduled by a contractor via Hello! on 8/26/2005 at 7:24:29 AM. Contact: ###-####. ok to final
ELE05-03109 Temporary Service8/25/20058/26/20058/26/2005 8:05:28 AMAPASS
Scheduled by a contractor via Hello! on 8/25/2005 at 1:26:16 PM. Contact: ###-####. corr made, t/s o/h n ok