ELE05-02841
| Temporary Service | 8/24/2005 | 8/26/2005 | 8/26/2005 4:22:07 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/24/2005 at 5:17:48 PM. Contact: ###-####. called contr, left corr notice 250.24 bonding jumper shall be connected between gec and grounded conductor, 250.53(G) ground rod shall be 8' long and flush with or below ground, 312.5 conductors entering enclosure shall have abrasion protection, fee due
|
ELE05-02824
| Temporary Service | 8/24/2005 | 8/26/2005 | 8/26/2005 4:18:18 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/24/2005 at 5:18:42 PM. Contact: ###-####. called contr, left corr notice, fee due. 312.5 conductors entering cnclosure shall have abrasion protection, 110.12(C) there shall be no broken parts, 250.56 supplementary ground rod shall be installed (8'-0" long)
|
ELE05-03070
| Temporary Service | 8/26/2005 | 8/26/2005 | 8/26/2005 4:14:52 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas 404.8 center of breaker handle shall be max 6'-7" above floor, 312.5 all conductors entering enclosure shall have abrasion protection,250.92(A) metal parts of service equipment shall be bonded,408.4 circuit directory shall be provided, re-inspection fee due,called contr, left corr notice
|
ELE05-03125
| Electrical Rough-In | 8/26/2005 | 8/26/2005 | 8/26/2005 2:30:06 PM | P | PASS |
|
|
###-#### ric ok walls and clg, service will do later
|
ELE05-02200
| Final | 8/26/2005 | 8/26/2005 | 8/26/2005 2:09:06 PM | P | PASS |
|
|
lloyd --call 1st for access ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final
|
ELE05-02446
| Permanent Service | 8/26/2005 | 8/26/2005 | 8/26/2005 1:21:22 PM | P | PASS |
|
|
Service ready, please contact Julian for service location, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters p/s u/g exst ok
|
ELE05-02808
| Final | 8/26/2005 | 8/26/2005 | 8/26/2005 10:35:56 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 8/26/2005 at 7:22:55 AM. talked to contr. will recall
|
ELE05-03116
| Permanent Service | 8/25/2005 | 8/26/2005 | 8/26/2005 10:33:20 AM | A | FAIL |
|
|
###-#### - bill Told owner to drive 2 gnd rods and install at service with #6 copper bare. rest ok
|
ELE05-03114
| Conference | 8/25/2005 | 8/26/2005 | 8/26/2005 9:35:57 AM | A | DONE |
|
|
###-#### - JEAN NOTE: PLEASE 1/2 HR PRIOR TO INSPECTION talked about new service, etc.
|
ELE05-03112
| Electrical Rough-In | 8/25/2005 | 8/26/2005 | 8/26/2005 8:47:02 AM | A | PASS |
|
|
ANY QUESTIONS PLEASE CALL ED SCHALLOCK; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ric ok. 3 rooms with walls demo and lite sws to 3-way, add few cut-in recpts.
|
ELE05-02489
| Final | 8/26/2005 | 8/26/2005 | 8/26/2005 8:19:07 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/26/2005 at 7:24:29 AM. Contact: ###-####. ok to final
|
ELE05-03109
| Temporary Service | 8/25/2005 | 8/26/2005 | 8/26/2005 8:05:28 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/25/2005 at 1:26:16 PM. Contact: ###-####. corr made, t/s o/h n ok
|