Inspections for the day of: Friday, August 26, 2005.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01718 FIRE-Final Inspection8/26/20058/26/20058/26/2005 5:14:22 PMPFAIL
Two duct smoke detectors failed to shut down units upon activation, all other items are okay.
BLD05-01484 FIRE-Final Inspection8/26/20058/26/20058/26/2005 4:23:59 PMPPART
Temporary occupancy approved with Sam Rogers permission pending the installation of HVAC duct smoke detectors.
FIR05-00338 INSP-Sprinkler Rough-in8/26/20058/26/20058/26/2005 4:13:47 PMPCANC
Canceled inspection, will schedule for monday the 29th.
FIR05-00448 INSP-Final Inspection8/26/20058/26/20058/26/2005 4:12:00 PMPPASS
Fire sprinkler permit finaled.
FIR05-00463 INSP-Final Inspection8/26/20058/26/20058/26/2005 3:45:17 PMPPASS
Permit for demo is finaled.
MIS05-00127 FIR-Final8/24/20058/26/20058/26/2005 3:33:47 PMPFAIL
Need to provide a current annual inspection for the fire sprinkler system, provide approved door hardware at the office and restroom doors, remove tape from the sprinkler heads, verify fire sprinkler permit for one head that has been removed.
BLD05-00127 FIRE-Final Inspection8/25/20058/26/20058/26/2005 3:30:05 PMPCANC
Spoke with Steve to reschedule inspection for Monday the 29th.
BLD05-00232 FIRE-Final Inspection8/25/20058/26/20058/26/2005 3:10:01 PMPNR
Canceled inspection per contractor, project is not complete.
FIR05-00446 INSP-Supply line flush8/24/20058/26/20058/26/2005 2:35:52 PMAPART
Underground hydrostatic test passed within allowabe leakage requirements, the flush performed after hydro test was satisfactory.
BLD05-00874 FIRE-Final Inspection8/26/20058/26/20058/26/2005 2:32:41 PMPFAIL
. Contact: ###-####. No power to exit sign/emergency light or emergency discharge light to enable testing or verify illumination.
FIR04-00737 INSP-Final Inspection8/26/20058/26/20058/26/2005 1:57:00 PMPFAIL
Exposed CPVC line in attic space needs tenting, one branch line has the deflectors oriented opposite the roof pitch, provide approved lateral restraint for all sprig-ups over 4' in length, perform a hydrostatic test due to the number of changes and additional heads installed for the correction of spacing issues in the attic.
FIR05-00155 INSP-Final Inspection8/26/20058/26/20058/26/2005 1:49:07 PMPCANC
This re-inspection is cancelled due to time constraints.
FIR05-00186 INSP-Final Inspection8/25/20058/26/20058/26/2005 1:35:55 PMAPART
Finished testing central riser stack, tested east riser, tested tamper in pit, need to install and test outside electric bell at riser next to mongolian bistro, testing complete through FP1.4.
BLD05-01200 FIRE-Final Inspection8/26/20058/26/20058/26/2005 11:01:05 AMPFAIL
Need fire alarm permit inspection and sign off prior to life safety final.
MIS05-00132 FIR-Final8/25/20058/26/20058/26/2005 10:57:05 AMAFAIL
Repair two exit signs/emergency lights at west corner of building, provide fire extinguishers as discussed, provide current inspection on fire sprinkler system, correct code defficiencies on sprinkler system, repair door hardware at back office.
FIR05-00155 INSP-Final Inspection8/25/20058/26/20058/26/2005 9:32:42 AMAFAIL
The flow switch failed to function under test conditions, provide forward flow test, provide "911 sign" at outside bell, install all escutcheons.
FIR05-00412 INSP-Final Inspection8/25/20058/26/20058/26/2005 9:30:12 AMAFAIL
The electrical outlet below hood failed to cut power post hood suppresion system operation.
FIR05-00044 INSP-Final Inspection8/25/20058/26/20058/26/2005 9:27:34 AMAFAIL
The strobe lens on several notification devices throughout areas A and B are below the allowed height AFF for wall mounted applications.
BLD05-02158 FIRE-Final Inspection8/26/20058/26/20058/26/2005 12:00:00 AMPPART
1. Need correct door hardware on 3 classroom doors.
2. Need (alarm) instructions in main building Knox Box.
3. NAC panel batteries to be changed from 8 a-h to 7 a-h, please verify.

joe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore