BLD05-01718
| FIRE-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 5:14:22 PM | P | FAIL |
|
|
Two duct smoke detectors failed to shut down units upon activation, all other items are okay.
|
BLD05-01484
| FIRE-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 4:23:59 PM | P | PART |
|
|
Temporary occupancy approved with Sam Rogers permission pending the installation of HVAC duct smoke detectors.
|
FIR05-00338
| INSP-Sprinkler Rough-in | 8/26/2005 | 8/26/2005 | 8/26/2005 4:13:47 PM | P | CANC |
|
|
Canceled inspection, will schedule for monday the 29th.
|
FIR05-00448
| INSP-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 4:12:00 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR05-00463
| INSP-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 3:45:17 PM | P | PASS |
|
|
Permit for demo is finaled.
|
MIS05-00127
| FIR-Final | 8/24/2005 | 8/26/2005 | 8/26/2005 3:33:47 PM | P | FAIL |
|
|
Need to provide a current annual inspection for the fire sprinkler system, provide approved door hardware at the office and restroom doors, remove tape from the sprinkler heads, verify fire sprinkler permit for one head that has been removed.
|
BLD05-00127
| FIRE-Final Inspection | 8/25/2005 | 8/26/2005 | 8/26/2005 3:30:05 PM | P | CANC |
|
|
Spoke with Steve to reschedule inspection for Monday the 29th.
|
BLD05-00232
| FIRE-Final Inspection | 8/25/2005 | 8/26/2005 | 8/26/2005 3:10:01 PM | P | NR |
|
|
Canceled inspection per contractor, project is not complete.
|
FIR05-00446
| INSP-Supply line flush | 8/24/2005 | 8/26/2005 | 8/26/2005 2:35:52 PM | A | PART |
|
|
Underground hydrostatic test passed within allowabe leakage requirements, the flush performed after hydro test was satisfactory.
|
BLD05-00874
| FIRE-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 2:32:41 PM | P | FAIL |
|
|
. Contact: ###-####. No power to exit sign/emergency light or emergency discharge light to enable testing or verify illumination.
|
FIR04-00737
| INSP-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 1:57:00 PM | P | FAIL |
|
|
Exposed CPVC line in attic space needs tenting, one branch line has the deflectors oriented opposite the roof pitch, provide approved lateral restraint for all sprig-ups over 4' in length, perform a hydrostatic test due to the number of changes and additional heads installed for the correction of spacing issues in the attic.
|
FIR05-00155
| INSP-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 1:49:07 PM | P | CANC |
|
|
This re-inspection is cancelled due to time constraints.
|
FIR05-00186
| INSP-Final Inspection | 8/25/2005 | 8/26/2005 | 8/26/2005 1:35:55 PM | A | PART |
|
|
Finished testing central riser stack, tested east riser, tested tamper in pit, need to install and test outside electric bell at riser next to mongolian bistro, testing complete through FP1.4.
|
BLD05-01200
| FIRE-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 11:01:05 AM | P | FAIL |
|
|
Need fire alarm permit inspection and sign off prior to life safety final.
|
MIS05-00132
| FIR-Final | 8/25/2005 | 8/26/2005 | 8/26/2005 10:57:05 AM | A | FAIL |
|
|
Repair two exit signs/emergency lights at west corner of building, provide fire extinguishers as discussed, provide current inspection on fire sprinkler system, correct code defficiencies on sprinkler system, repair door hardware at back office.
|
FIR05-00155
| INSP-Final Inspection | 8/25/2005 | 8/26/2005 | 8/26/2005 9:32:42 AM | A | FAIL |
|
|
The flow switch failed to function under test conditions, provide forward flow test, provide "911 sign" at outside bell, install all escutcheons.
|
FIR05-00412
| INSP-Final Inspection | 8/25/2005 | 8/26/2005 | 8/26/2005 9:30:12 AM | A | FAIL |
|
|
The electrical outlet below hood failed to cut power post hood suppresion system operation.
|
FIR05-00044
| INSP-Final Inspection | 8/25/2005 | 8/26/2005 | 8/26/2005 9:27:34 AM | A | FAIL |
|
|
The strobe lens on several notification devices throughout areas A and B are below the allowed height AFF for wall mounted applications.
|
BLD05-02158
| FIRE-Final Inspection | 8/26/2005 | 8/26/2005 | 8/26/2005 12:00:00 AM | P | PART |
|
|
1. Need correct door hardware on 3 classroom doors.
2. Need (alarm) instructions in main building Knox Box.
3. NAC panel batteries to be changed from 8 a-h to 7 a-h, please verify.
joe; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|