ELE08-01389
| ELE-Aging Inspection | 8/26/2008 | 8/26/2008 | 9/3/2008 9:50:00 AM | | DONE |
|
|
|
ELE08-02249
| Electrical Rough-In | 8/25/2008 | 8/26/2008 | 8/26/2008 3:24:58 PM | P | PART |
|
|
Underground conducts to remote garage and power company. Phone #: ###-#### Internet Inspection Request from: Roy Kay ok
|
ELE08-02373
| Electrical Rough-In | 8/26/2008 | 8/26/2008 | 8/26/2008 2:38:40 PM | P | PART |
|
|
If you have any questions please contact Rafael at the number given. Phone #: ###-#### Internet Inspection Request from: Vicki Moore no esc walls ok
|
ELE08-02357
| Rough-In Permanent Service | 8/26/2008 | 8/26/2008 | 8/26/2008 1:47:49 PM | P | FAIL |
|
|
service is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten corr called 250.64(E) shall choke both ends of nipple for GEC, 200.2(B) terminte GEC at neutral bus loose bond screw
|
ELE08-02372
| Temporary Service | 8/26/2008 | 8/26/2008 | 8/26/2008 12:53:13 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Bob Glenn t/s u/g new ok
|
ELE08-02363
| Permanent Service | 8/25/2008 | 8/26/2008 | 8/26/2008 11:55:47 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Robert Murray called owner needs plumbing permit, Eric checked out job
|
ELE07-03432
| ELE-Aging Inspection | 8/26/2008 | 8/26/2008 | 8/26/2008 10:13:50 AM | | PART |
|
|
wsuc
|
ELE08-01342
| ELE-Aging Inspection | 8/26/2008 | 8/26/2008 | 8/26/2008 10:13:30 AM | | DONE |
|
|
|
ELE08-01342
| Final | 8/26/2008 | 8/26/2008 | 8/26/2008 10:13:21 AM | A | PASS |
|
|
|
ESC08-00507
| General Inspection | 8/26/2008 | 8/26/2008 | 8/26/2008 9:56:04 AM | A | PART |
|
|
ok
|
ELE08-02369
| Electrical Rough-In | 8/25/2008 | 8/26/2008 | 8/26/2008 9:55:19 AM | A | PART |
|
|
jesse Phone #: ###-#### sun rm ok called contr will correct wiring owner did, and check romex at bushing through alum framing
|
ELE08-02368
| Rough-In Permanent Service | 8/25/2008 | 8/26/2008 | 8/26/2008 8:58:10 AM | A | FAIL |
|
|
Phone #: ###-#### corr. called 110.26(F)(2) remove gas pipe below p/s, 250.52 (A)(1) or 104(A)(1) grd or bond water pipe, 310.16 needs 250 KC mill 310.8 needs sunlight resistence wire
|
ELE07-04131
| Electrical Rough-In | 8/25/2008 | 8/26/2008 | 8/26/2008 8:11:40 AM | A | PART |
|
|
cover inspection for the front recepction desk Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok
|
ELE08-02357
| Rough-In Permanent Service | 8/25/2008 | 8/26/2008 | 8/26/2008 8:08:53 AM | A | CANC |
|
|
service is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten Inspection cancelled from web by: gary batten
|
ELE08-02363
| Final | 8/25/2008 | 8/26/2008 | 8/25/2008 9:42:57 PM | A | CANC |
|
|
This will be a permanate service Phone #: ###-#### Internet Inspection Request from: Robert Murray Inspection cancelled from web by: Robert Murray
|
ELE08-02363
| Final | 8/25/2008 | 8/26/2008 | 8/25/2008 11:12:08 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Robert Murray Inspection cancelled from web by: Robert Murray
|