Inspections for the day of: Wednesday, August 26, 2009.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00808 FIRE-Final Inspection8/26/20098/26/20098/27/2009 7:43:10 AMPCANC
Cancelled due to time constraints.
BLD09-01407 FIRE-Final Inspection8/26/20098/26/20098/26/2009 3:58:21 PMPPART
A temporary occupancy was given until approved single action hardware is provided at the main exit and the thumbturn removed or keyed hardware is provided, with sticker, and pul handle. Also the manual bolt from across the rear exit door needs removed and the door hardware repaired.
BLD09-01406 FIRE-Final Inspection8/26/20098/26/20098/26/2009 3:56:00 PMPCANC
Cancelled due to time constraints.
FIR07-00515 INSP-Sprinkler Rough-in/Hydro8/25/20098/26/20098/26/2009 3:52:08 PMPCANC
Cancelled due to time constraints.
FIR09-00453 INSP-Final Inspection8/26/20098/26/20098/26/2009 3:50:37 PMPPART
All items tested ok but as-builts are needed that reflect the changes as discussed.
FIR09-00317 INSP-Sprinkler Rough-in8/26/20098/26/20098/26/2009 3:36:53 PMPCANC
Cancelled due to time constraints.
FIR09-00242 INSP-Final Inspection8/25/20098/26/20098/26/2009 3:23:43 PMACANC
Cancelled due to time constraints. No inspection was performed.
FIR09-00434 INSP-Final Inspection8/25/20098/26/20098/26/2009 3:23:23 PMACANC
Cancelled due to time constraints. No inspection was performed.
FIR09-00483 INSP-Sprinkler Rough-in8/25/20098/26/20098/26/2009 2:36:16 PMACANC
Canceled due to time constraints. No inspection performed.
BLD09-01062 FIRE-Alarm Testing8/26/20098/26/20098/26/2009 2:22:44 PMADONE
See previous entry.
BLD09-01062 FIRE-Final Inspection8/26/20098/26/20098/26/2009 2:22:10 PMAPART
A temporary occupancy is being given with scott and marks approval. The remaining items are provide additional emergency lighting as marked on the electrical sheet, provide missing hardware and exit signs in the board room, provide occupant load signs for the conference rooms, provide correct smoke detector coverage in room 176, provide verification that the velocity listing for the underfloor detectors has not been exceeded, provide maps at both fire panels as discussed and test the server room liebert units for shutdown.
FIR09-00451 INSP-Alarm Testing8/26/20098/26/20098/26/2009 2:19:09 PMPPART
A temporary occupancy was given with scott and marks approval. An updated map needs to be provided at the facp as discussed that shows the actual number and location of the duct smoke detectors.
FIR09-00424 INSP-Final Inspection8/25/20098/26/20098/26/2009 2:17:38 PMAPASS
Permit finaled
FIR09-00424 INSP-Final Inspection8/25/20098/26/20098/26/2009 2:17:17 PMAPASS
Permit finaled
FIR09-00164 INSP-Sprinkler Rough-in/Hydro8/25/20098/26/20098/26/2009 2:16:52 PMPCANC
Cancelled due to time constraints. No inspection was performed.
FIR08-00840 INSP-Final Inspection8/25/20098/26/20098/26/2009 9:41:11 AMAFAIL
Blocked pendant heads in closets and missing partial ceiling in large mechanical room.
FIR08-00839 INSP-Final Inspection8/25/20098/26/20098/26/2009 9:40:01 AMAFAIL
Blocked pendants in closets
FIR08-00838 INSP-Final Inspection8/25/20098/26/20098/26/2009 9:39:13 AMAFAIL
Pendant is too far off of wall in kitchen/dining area, head is still taped up in room under stairs and pendants are blocked by light fixtures in closets.
FIR08-00446 INSP-Final Inspection8/25/20098/26/20098/26/2009 9:38:06 AMAFAIL
One pendant in the master bath is overspaced from west wall, need ceiling and pendant installed in furnance room and the permanent lighting needs installed.