Inspections for the day of: Thursday, August 26, 2010.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00407 INSP-Sprinkler Rough-in8/26/20108/26/20108/27/2010 3:36:33 PMPCANC
Terry-Underground 5 feet out for cover inspection please Phone #: ###-####
BLD09-02032 FIRE-Final Inspection8/26/20108/26/20108/26/2010 3:35:26 PMPFAIL
An outside supply duct has been added to the unit. This new duct is connected to the hvac unit before the duct detector which would delute any smoke from within the compartment. This new ducting needs to be connected to the hvac unit after the duct smoke detector. No testing was performed.
FIR10-00359 INSP-Final Inspection8/24/20108/26/20108/26/2010 3:26:22 PMPPASS
Permit finaled
FIR10-00322 INSP-Final Inspection8/26/20108/26/20108/26/2010 2:35:46 PMPPASS
permit finaled
FIR10-00339 INSP-Sprinkler Rough-in8/26/20108/26/20108/26/2010 1:54:48 PMPPASS
Sprinkler piping is ok to cover. Per Lonnie and I's conversation, 8" lintels will be installed at the shower/soffit to avoid instlling sprinkler pendants in the showers.
BLD10-02012 FIRE-Final Inspection8/25/20108/26/20108/26/2010 12:20:51 PMAFAIL
Provide missing sprinkler coverage in the closet located in the kitchen area and final inspections need to be passed on the two AES panels installed by simplexgrinnell
FIR10-00342 INSP-Sprinkler Rough-in8/25/20108/26/20108/26/2010 11:28:29 AMAPASS
The sprinkler piping in the drop ceiling areas can be covered.
FIR10-00336 INSP-Final Inspection8/25/20108/26/20108/26/2010 11:23:15 AMAFAIL
The audio/visual devices are mounted too low. Need to test the a/v's and the smoke detectors. The tamper switch and flow switch were verified.
FIR10-00224 INSP-Final Inspection8/25/20108/26/20108/26/2010 11:20:48 AMAFAIL
The duct smoke detectors have not been installed correctly on the mechanical duct work. This was reverified with Bernie with system sensor tech support. Testing was stopped.
FIR10-00286 INSP-Sprinkler Rough-in8/25/20108/26/20108/26/2010 11:19:13 AMAPASS
The sprinkler piping as marked on the plans can be covered. This includes the piping at the store entry and the back rooms.
BLD10-01869 FIRE-Final Inspection8/25/20108/26/20108/26/2010 11:17:31 AMAPASS
Life safety passed