FIR10-00407
| INSP-Sprinkler Rough-in | 8/26/2010 | 8/26/2010 | 8/27/2010 3:36:33 PM | P | CANC |
|
|
Terry-Underground 5 feet out for cover inspection please Phone #: ###-####
|
BLD09-02032
| FIRE-Final Inspection | 8/26/2010 | 8/26/2010 | 8/26/2010 3:35:26 PM | P | FAIL |
|
|
An outside supply duct has been added to the unit. This new duct is connected to the hvac unit before the duct detector which would delute any smoke from within the compartment. This new ducting needs to be connected to the hvac unit after the duct smoke detector. No testing was performed.
|
FIR10-00359
| INSP-Final Inspection | 8/24/2010 | 8/26/2010 | 8/26/2010 3:26:22 PM | P | PASS |
|
|
Permit finaled
|
FIR10-00322
| INSP-Final Inspection | 8/26/2010 | 8/26/2010 | 8/26/2010 2:35:46 PM | P | PASS |
|
|
permit finaled
|
FIR10-00339
| INSP-Sprinkler Rough-in | 8/26/2010 | 8/26/2010 | 8/26/2010 1:54:48 PM | P | PASS |
|
|
Sprinkler piping is ok to cover. Per Lonnie and I's conversation, 8" lintels will be installed at the shower/soffit to avoid instlling sprinkler pendants in the showers.
|
BLD10-02012
| FIRE-Final Inspection | 8/25/2010 | 8/26/2010 | 8/26/2010 12:20:51 PM | A | FAIL |
|
|
Provide missing sprinkler coverage in the closet located in the kitchen area and final inspections need to be passed on the two AES panels installed by simplexgrinnell
|
FIR10-00342
| INSP-Sprinkler Rough-in | 8/25/2010 | 8/26/2010 | 8/26/2010 11:28:29 AM | A | PASS |
|
|
The sprinkler piping in the drop ceiling areas can be covered.
|
FIR10-00336
| INSP-Final Inspection | 8/25/2010 | 8/26/2010 | 8/26/2010 11:23:15 AM | A | FAIL |
|
|
The audio/visual devices are mounted too low. Need to test the a/v's and the smoke detectors. The tamper switch and flow switch were verified.
|
FIR10-00224
| INSP-Final Inspection | 8/25/2010 | 8/26/2010 | 8/26/2010 11:20:48 AM | A | FAIL |
|
|
The duct smoke detectors have not been installed correctly on the mechanical duct work. This was reverified with Bernie with system sensor tech support. Testing was stopped.
|
FIR10-00286
| INSP-Sprinkler Rough-in | 8/25/2010 | 8/26/2010 | 8/26/2010 11:19:13 AM | A | PASS |
|
|
The sprinkler piping as marked on the plans can be covered. This includes the piping at the store entry and the back rooms.
|
BLD10-01869
| FIRE-Final Inspection | 8/25/2010 | 8/26/2010 | 8/26/2010 11:17:31 AM | A | PASS |
|
|
Life safety passed
|