ELE15-02401
| Electrical Rough-In | 8/26/2015 | 8/26/2015 | 8/26/2015 2:29:38 PM | P | PART |
|
|
underground; Perry Phone #: ###-#### ok cover u/g at t/s, talked to contractor about breakers and so cord, he will make compatible, could not locate plans, contractor will mark as required
|
ELE15-02702
| Rough-In Permanent Service | 8/26/2015 | 8/26/2015 | 8/26/2015 2:02:17 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn ri ok, p/s u/g n ok
|
ELE15-02715
| Temporary Service | 8/26/2015 | 8/26/2015 | 8/26/2015 12:59:23 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Douglas Hackney called, left correction notice, NEC 240.24(A) center of upper breaker handle shall not be over 6'7", 250.53(G) upper end ground rod shall be flush with or below grade, BCC IPCO meter shall be 5' 6" above grade, shall clean foreign material off electrical gear
|
ELE15-02707
| Rough-In Permanent Service | 8/26/2015 | 8/26/2015 | 8/26/2015 12:04:48 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk ri ok, p/s u/g n ok
|
ELE15-01886
| Final | 8/26/2015 | 8/26/2015 | 8/26/2015 11:31:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn ok final
|
ELE15-02630
| Temporary Service | 8/25/2015 | 8/26/2015 | 8/26/2015 10:27:30 AM | A | PASS |
|
|
temp pole Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-02629
| Temporary Service | 8/25/2015 | 8/26/2015 | 8/26/2015 9:56:04 AM | A | PASS |
|
|
temp pole Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-01959
| Final | 8/26/2015 | 8/26/2015 | 8/26/2015 9:18:16 AM | A | PASS |
|
|
CODE 4224 ANY ? CALL BILL ###-#### Phone #: ###-#### Inspection requested via web by Bob Glenn ok final
|
ELE15-01334
| Final | 8/26/2015 | 8/26/2015 | 8/26/2015 8:39:25 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey called, left correction notice, NEC 210.63 sh-all provide receptacle within 25' of a/c- 2 places, 210.52(A)(1) no point along floor line shall be over 6' from receptacle-lower slider, 406.9 shall install w/p receptace and in-use cover on patio
|