Inspections for the day of: Wednesday, August 26, 2015.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-02257 FIRE-Final Inspection8/26/20158/26/20158/26/2015 3:34:40 PMPCANC
Rescheduled for friday.
FIR15-00356 INSP-Sprinkler Rough-in8/25/20158/26/20158/26/2015 3:31:44 PMPPASS
24 hour air test passed
FIR15-00153 INSP-Final Inspection8/26/20158/26/20158/26/2015 2:49:37 PMPFAIL
The only items test today was verifying the facp and nac panels, phone lines, elevator recall and fire sprinkler flow and tamper switches. I noted that the elevator power needs to be monitored but hat functions can remain as-is, all of the wall mount strobes are mounted too low, many of the strobes are overspaced, additional notification devices are required on the third floor in the areas that are to remain occupied. As-builts with these corrections and corrected floor plan layout will be required. I did not inspect any of the first floor or basement today.
FIR15-00408 INSP-Sprinkler Rough-in8/25/20158/26/20158/26/2015 11:58:31 AMAPART
This is a partial rough to cover request. See the city approved plans for locations of hardlids areas that are ok to cover and the large shop area where the overhead rough-in piping has passed. Shop area is not ok to cover until another rough-in has passed for the drop sprinklers. Seismic bracing on branchlines still needs to be verified since nothing was address on the drawings.
FIR15-00534 INSP-Sprinkler Rough-in8/25/20158/26/20158/26/2015 10:17:55 AMAPASS
underground supply line ok to cover
FIR15-00215 INSP-Sprinkler Rough-in8/26/20158/26/20158/26/2015 10:16:12 AMPPASS
Tenting and rough-in passed. Piping can be covered.
BLD15-00495 FIRE-Final Inspection8/25/20158/26/20158/26/2015 8:52:00 AMAPASS
life safety passed
BLD15-02156 FIRE-Final Inspection8/26/20158/26/20158/26/2015 8:50:21 AMPPASS
Life safety passed
FIR15-00590 INSP-Final Inspection8/25/20158/26/20158/26/2015 8:49:50 AMAPASS
Permit finaled