ELE97-02811
| INSP - Electrical Rough-In | 8/27/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | | PASS |
|
|
/ / 403 - WALLS OK TO COVER.
|
ELE97-01991
| INSP - Permanent service | 8/26/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | A | FAIL |
|
|
08/26/97 403 - If you have problems when you get there, call me - Jim S. NEC: 230-6. UNFUSED CONDUCTORS ENTERING BUILDING. NEC: 250. SERVICES SHALL HAVE GROUNDING CONDUCTOR.
|
ELE97-02274
| INSP - Final | 8/26/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | A | FAIL |
|
|
08/26/97 403 - NEC: 424-65. DUCT HEATERS SHALL DISCONNECTING MEANS WITHIN SIGHT OF CONTROLLER.
|
ELE97-00798
| INSP - Final | 8/26/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | A | PASS |
|
|
08/26/97 403 -
|
ELE97-01884
| INSP - Electrical Rough-In | 8/27/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | P | PASS |
|
|
08/27/97 403 - rough-in on garage
|
ELE97-01891
| INSP - Final | 8/26/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | P | PASS |
|
|
08/27/97 403 - I brought this from yestereday, Jim S. THREE OFFICES ARE UNDER TEMP/OCC PENDING RESULTS OF FIRE DEPT. DECISSION CONCERNING SPRINKLER SYSTEM.
|
ELE97-02455
| INSP - Permanent service | 8/27/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | P | FAIL |
|
|
08/27/97 403 - BCEC: GUY-WIRE KIT OR U-BOLT REQUIRED FOR SERVICE MAST.
|
ELE97-02759
| INSP - Electrical Rough-In | 8/26/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | P | PART |
|
|
08/27/97 403 - early p.m.
|
ELE97-02811
| INSP - Ele Rough-In/Perm Svc | 8/26/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | P | FAIL |
|
|
08/27/97 403 - NO GROUNDING UFER. NEC: 250-81(C). GROUNDING ELECTRODE THAN NO.#4 COPPER AND 20FT. IN LENGTH, SHALL BE INCASED IN 2IN. OF CONCRETE.
|
ELE97-02818
| INSP - Electrical Rough-In | 8/27/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | P | PART |
|
|
08/27/97 403 - NORTH WALL.
|
ELE97-02835
| INSP - Permanent service | 8/26/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | P | CANC |
|
|
08/26/97 403 - CONTRACTORS REQUEST, WILL RESCHEDULE.
|
ELE97-02870
| INSP - Electrical Rough-In | 8/27/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | P | PASS |
|
|
08/27/97 403 -
|
ELE97-02881
| INSP - T/S and Final | 8/27/1997 | 8/27/1997 | 8/27/1997 12:00:00 AM | P | CANC |
|
|
08/27/97 403 - TEMPORARY POWER POLE NOT INSTALLED FOR INSPECTION. REINSPECTION FEE REQUESTED.
|