Inspections for the day of: Wednesday, August 27, 1997.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE97-02811 INSP - Electrical Rough-In8/27/19978/27/19978/27/1997 12:00:00 AM PASS
/ / 403 - WALLS OK TO COVER.
ELE97-01991 INSP - Permanent service8/26/19978/27/19978/27/1997 12:00:00 AMAFAIL
08/26/97 403 - If you have problems when you get there, call me - Jim S. NEC: 230-6. UNFUSED CONDUCTORS ENTERING BUILDING. NEC: 250. SERVICES SHALL HAVE GROUNDING CONDUCTOR.
ELE97-02274 INSP - Final8/26/19978/27/19978/27/1997 12:00:00 AMAFAIL
08/26/97 403 - NEC: 424-65. DUCT HEATERS SHALL DISCONNECTING MEANS WITHIN SIGHT OF CONTROLLER.
ELE97-00798 INSP - Final8/26/19978/27/19978/27/1997 12:00:00 AMAPASS
08/26/97 403 -
ELE97-01884 INSP - Electrical Rough-In8/27/19978/27/19978/27/1997 12:00:00 AMPPASS
08/27/97 403 - rough-in on garage
ELE97-01891 INSP - Final8/26/19978/27/19978/27/1997 12:00:00 AMPPASS
08/27/97 403 - I brought this from yestereday, Jim S. THREE OFFICES ARE UNDER TEMP/OCC PENDING RESULTS OF FIRE DEPT. DECISSION CONCERNING SPRINKLER SYSTEM.
ELE97-02455 INSP - Permanent service8/27/19978/27/19978/27/1997 12:00:00 AMPFAIL
08/27/97 403 - BCEC: GUY-WIRE KIT OR U-BOLT REQUIRED FOR SERVICE MAST.
ELE97-02759 INSP - Electrical Rough-In8/26/19978/27/19978/27/1997 12:00:00 AMPPART
08/27/97 403 - early p.m.
ELE97-02811 INSP - Ele Rough-In/Perm Svc8/26/19978/27/19978/27/1997 12:00:00 AMPFAIL
08/27/97 403 - NO GROUNDING UFER. NEC: 250-81(C). GROUNDING ELECTRODE THAN NO.#4 COPPER AND 20FT. IN LENGTH, SHALL BE INCASED IN 2IN. OF CONCRETE.
ELE97-02818 INSP - Electrical Rough-In8/27/19978/27/19978/27/1997 12:00:00 AMPPART
08/27/97 403 - NORTH WALL.
ELE97-02835 INSP - Permanent service8/26/19978/27/19978/27/1997 12:00:00 AMPCANC
08/26/97 403 - CONTRACTORS REQUEST, WILL RESCHEDULE.
ELE97-02870 INSP - Electrical Rough-In8/27/19978/27/19978/27/1997 12:00:00 AMPPASS
08/27/97 403 -
ELE97-02881 INSP - T/S and Final8/27/19978/27/19978/27/1997 12:00:00 AMPCANC
08/27/97 403 - TEMPORARY POWER POLE NOT INSTALLED FOR INSPECTION. REINSPECTION FEE REQUESTED.