Inspections for the day of: Wednesday, August 27, 2003.
Number of inspections: 18
Percentage of inspections complete: 94 %
Percentage of inspections not complete: 6 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00187 INSP-Final Inspection8/26/20038/26/2003 A 
FIR03-00154 FIR-Aging Inspection8/27/20038/27/20038/27/2003 12:00:00 AM PASS
this building is still under construction 8/27/2003 7:02:49 AM
FIR03-00493 INSP-Final Inspection8/26/20038/27/20038/27/2003 12:00:00 AMAPASS
###-#### don
FIR03-00247 INSP-Final Inspection8/27/20038/27/20038/27/2003 12:00:00 AMAPASS
FIR03-00141 INSP-Final Inspection8/27/20038/27/20038/27/2003 12:00:00 AMAFAIL
left correction notice with GC; detectors overspaced in corridor; strobes overspaced in corridor and hospitality room; need descriptors for PIV and hall detectors; strobes acitivate when alarm silence is pushed after ADA room detector is in alarm??; open splices in fire wire throughout; need map and as-builts due to many changes for mapnet ID #'s and location of devices and splitting of NAC's; will need to test panel for troubles - phone lines, batt's, NAC's for voltage drop, etc; record of completion 8/27/2003 3:40:20 PM
FIR03-00152 INSP-Final Inspection8/26/20038/27/20038/27/2003 12:00:00 AMAFAIL
julio; Phone #: ###-#### Internet Inspection Request from: Marc Lileks fire sprinkler control signs on doors; SFD not closing on third floor west; doors not latching in rated assemblies; emergency lights not on corridor lighting circuits; need hazardous chem sign on pool door; see fire alarm permit for fire alarm items; 8/27/2003 3:44:41 PM
FIR03-00069 INSP-Sprinkler Rough-in/Hydro8/26/20038/27/20038/27/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/26/2003 at 8:42:17 AM. Contact: ###-####.
FIR03-00136 INSP-Sprinkler Rough-in/Hydro8/26/20038/27/20038/27/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/26/2003 at 8:43:42 AM. Contact: ###-####.
FIR03-00137 INSP-Sprinkler Rough-in/Hydro8/26/20038/27/20038/27/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/26/2003 at 8:46:54 AM. Contact: ###-####.
FIR03-00135 INSP-Sprinkler Rough-in/Hydro8/26/20038/27/20038/27/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/26/2003 at 10:23:43 AM. Contact: ###-####.
FIR03-00115 INSP-Sprinkler Rough-in/Hydro8/26/20038/27/20038/27/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/26/2003 at 10:25:11 AM. Contact: ###-####.
FIR03-00138 INSP-Sprinkler Rough-in/Hydro8/26/20038/27/20038/27/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/26/2003 at 10:27:05 AM. Contact: ###-####.
FIR03-00139 INSP-Sprinkler Rough-in/Hydro8/26/20038/27/20038/27/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/26/2003 at 10:28:33 AM. Contact: ###-####.
FIR03-00426 INSP-Sprinkler Rough-in8/27/20038/27/20038/27/2003 12:00:00 AMPPART
russ; Phone #: ###-#### Internet Inspection Request from: Marc Lileks okay to cover 2nd floor restrooms only; minor modifications made in this area due to concrete wall - okay 8/27/2003 1:24:40 PM
BLD03-01052 FIRE-Final Inspection8/27/20038/27/20038/27/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 8/27/2003 at 8:59:11 AM. Contact: ###-####. fire will be on temp occupancy per agreement with Dave Miller; on temp pending approval of fire alarm plans for the new duct detectors for AHU shutdown 8/27/2003 2:04:25 PM
FIR03-00365 INSP-Final Inspection8/27/20038/27/20038/27/2003 12:00:00 AMPPASS
FIR03-00071 INSP-Final Inspection8/27/20038/27/20038/27/2003 12:00:00 AMPPASS
FIR03-00152 INSP-Final Inspection8/27/20038/27/20038/27/2003 12:00:00 AMPPASS