Inspections for the day of: Wednesday, August 27, 2003.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00266 FIR-Aging Inspection8/27/20038/27/20038/27/2003 12:00:00 AM PASS
FIR03-00463 INSP-Final Inspection8/21/20038/27/20038/27/2003 12:00:00 AMAFAIL
please call first//###-#### don Connect the hood suppresion system to the existing fire alarm system. This work will need to be permited. Provide a barrier between the range and the fryer. Hang fire extinguishers. Provide test/submittals at final 8/27/2003 9:46:09 AM
FIR03-00062 INSP-Final Inspection8/26/20038/27/20038/27/2003 12:00:00 AMAFAIL
ralph; Phone #: ###-#### Hood system, inside tamper vavles and the wet flow switch worked correctly. Other items such as the low air and the PIV did not. The alarm tech. did not know how to test the batteries on the panel and the D8132 module say 15ah max battery but the cut sheet states 18ah. Tech support never did answer their line for us to get answers 8/27/2003 2:13:44 PM
BLD03-01634 FIRE-Final Inspection8/26/20038/27/20038/27/2003 12:00:00 AMAFAIL
Sprinkler pendant is overspaced near east exit, repair exit light out side the exit in egress corridor, test duct smoke detectors, remover thumb turn on west doors 8/27/2003 12:50:53 PM
BLD03-00987 FIRE-Final Inspection8/26/20038/27/20038/27/2003 12:00:00 AMAFAIL
sid--###-#### Items on correction notice not corrected in order to give temp occupancy 8/27/2003 10:58:23 AM
FIR03-00448 INSP-Sprinkler Rough-in/Hydro8/26/20038/27/20038/27/2003 12:00:00 AMAPART
Underground supply line is ok to cover. One section of the piping rises to within 4' of the existing grade but the excavator stated that another 10" of roadmix and then a layer of blacktop would be over it. I contacted Debest Fire and told them that I was giving an ok to cover and that if conduit was needed in the trench for PIV tamper they had better do it now. The control vavle location was not shown on the plans 8/27/2003 10:41:57 AM
FIR03-00265 INSP-Final Inspection8/27/20038/27/20038/27/2003 12:00:00 AMAPASS
FIR03-00239 INSP-Sprinkler Rough-in/Hydro8/27/20038/27/20038/27/2003 12:00:00 AMPPART
The underground supply between both buildings is ok to cover 8/28/2003 8:11:49 AM
FIR03-00442 INSP-Final Inspection8/27/20038/27/20038/27/2003 12:00:00 AMPCANC
duplicate inspection 8/27/2003 10:53:05 AM
FIR03-00442 INSP-Final Inspection8/27/20038/27/20038/27/2003 12:00:00 AMPPASS
DAVE ###-####