FIR03-00266
| FIR-Aging Inspection | 8/27/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | | PASS |
|
|
|
FIR03-00463
| INSP-Final Inspection | 8/21/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | A | FAIL |
|
|
please call first//###-#### don Connect the hood suppresion system to the existing fire alarm system. This work will need to be permited. Provide a barrier between the range and the fryer. Hang fire extinguishers. Provide test/submittals at final 8/27/2003 9:46:09 AM
|
FIR03-00062
| INSP-Final Inspection | 8/26/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | A | FAIL |
|
|
ralph; Phone #: ###-#### Hood system, inside tamper vavles and the wet flow switch worked correctly. Other items such as the low air and the PIV did not. The alarm tech. did not know how to test the batteries on the panel and the D8132 module say 15ah max battery but the cut sheet states 18ah. Tech support never did answer their line for us to get answers 8/27/2003 2:13:44 PM
|
BLD03-01634
| FIRE-Final Inspection | 8/26/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | A | FAIL |
|
|
Sprinkler pendant is overspaced near east exit, repair exit light out side the exit in egress corridor, test duct smoke detectors, remover thumb turn on west doors 8/27/2003 12:50:53 PM
|
BLD03-00987
| FIRE-Final Inspection | 8/26/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | A | FAIL |
|
|
sid--###-#### Items on correction notice not corrected in order to give temp occupancy 8/27/2003 10:58:23 AM
|
FIR03-00448
| INSP-Sprinkler Rough-in/Hydro | 8/26/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | A | PART |
|
|
Underground supply line is ok to cover. One section of the piping rises to within 4' of the existing grade but the excavator stated that another 10" of roadmix and then a layer of blacktop would be over it. I contacted Debest Fire and told them that I was giving an ok to cover and that if conduit was needed in the trench for PIV tamper they had better do it now. The control vavle location was not shown on the plans 8/27/2003 10:41:57 AM
|
FIR03-00265
| INSP-Final Inspection | 8/27/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | A | PASS |
|
|
|
FIR03-00239
| INSP-Sprinkler Rough-in/Hydro | 8/27/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | P | PART |
|
|
The underground supply between both buildings is ok to cover 8/28/2003 8:11:49 AM
|
FIR03-00442
| INSP-Final Inspection | 8/27/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | P | CANC |
|
|
duplicate inspection 8/27/2003 10:53:05 AM
|
FIR03-00442
| INSP-Final Inspection | 8/27/2003 | 8/27/2003 | 8/27/2003 12:00:00 AM | P | PASS |
|
|
DAVE ###-####
|