FIR03-00690
| INSP-Conference | 8/26/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | A | PART |
|
|
cliff; Phone #: ###-#### Internet Inspection Request from: Annette Moore Met with Cliff about testing the system; will need to verify smoke detectors on wall in room; need to verify wire size/calc's for NAC's prior to testing 8/27/2004 11:03:16 AM
|
BLD04-01338
| FIRE-Final Inspection | 8/26/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | A | PART |
|
|
###-#### - richard Phase I okay to occupy 8/27/2004 4:05:43 PM
|
BLD04-00919
| FIRE-Final Inspection | 8/26/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | A | PASS |
|
|
9:30
|
BLD03-02057
| FIRE-Final Inspection | 8/27/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/27/2004 at 8:30:47 AM. Contact: ###-####. See fire alarm permit 8/27/2004 4:16:25 PM
|
BLD03-02058
| FIRE-Final Inspection | 8/27/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/27/2004 at 8:32:56 AM. Contact: ###-####. Need access door for damper in corridor; add exit sign on 2nd floor; install knox box; see sprinkler and alarm permits for other info 8/27/2004 4:16:03 PM
|
BLD04-01466
| FIRE-Final Inspection | 8/27/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 8/27/2004 at 8:37:27 AM. Contact: ###-####.
|
FIR04-00174
| INSP-Final Inspection | 8/27/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | P | FAIL |
|
|
Your contact is Mike Bierman at ###-####; Phone #: ###-#### Internet Inspection Request from: Trent Bice Need clac sticker 8/27/2004 4:10:53 PM
|
FIR04-00424
| INSP-Final Inspection | 8/27/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | P | PART |
|
|
Phase I okay; NAC's operated in Phase I area okay; will need to test this circuit EOL voltage at final 8/27/2004 4:05:24 PM
|
FIR03-00814
| INSP-Final Inspection | 8/27/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | P | PASS |
|
|
UG completed 8/27/2004 4:06:48 PM
|
FIR04-00412
| INSP-Final Inspection | 8/27/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | P | FAIL |
|
|
LEd not working on AHU 5 detector; need updated maps to reflect changes; resubmittals needed due to initiating circuit changes; monitor elevator power as shown on plans 8/27/2004 4:09:47 PM
|
FIR04-00413
| INSP-Final Inspection | 8/27/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | P | FAIL |
|
|
Plans don't install - initiating devices don't match; update maps; resubmit plan mod's; monitor elevator power as shown on plans; need lockout on sprinkler bell breaker; need sign on FACP door; install knox box 8/27/2004 4:13:54 PM
|
FIR04-00418
| INSP-Final Inspection | 8/25/2004 | 8/27/2004 | 8/27/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 8/25/2004 at 8:28:26 AM. Contact: ###-####. Previously completed 8/27/2004 1:08:49 PM
|