Inspections for the day of: Friday, August 27, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00367 INSP-Final Inspection8/25/20048/27/20048/27/2004 12:00:00 AMAPASS
fire alarm finaled 8/27/2004 10:16:47 AM
FIR02-00366 INSP-Final Inspection8/26/20048/27/20048/27/2004 12:00:00 AMAPASS
fire alarm finaled. The single horn/strobe does not sound in a code 3 (temporal). It has 5 on, silence, then 6 on. Per ADT this output cannot be changed to temporal. This is a previously approved installation. 8/27/2004 11:07:00 AM
FIR04-00508 INSP-Final Inspection8/26/20048/27/20048/27/2004 12:00:00 AMAPASS
Fire alarm permit finaled 8/27/2004 1:30:02 PM
FIR04-00488 INSP-Sprinkler Rough-in/Hydro8/26/20048/27/20048/27/2004 12:00:00 AMAPART
Hard lid areas as marked on approved plans are ok to cover 8/27/2004 9:27:34 AM
FIR04-00434 INSP-Final Inspection8/26/20048/27/20048/27/2004 12:00:00 AMAFAIL
Provide revised plans and spare heads of rack type in the head box 8/27/2004 11:08:47 AM
FIR04-00300 INSP-Sprinkler Rough-in/Hydro8/26/20048/27/20048/27/2004 12:00:00 AMPPASS
24 hour air test passed 8/27/2004 2:04:10 PM
FIR04-00508 INSP-Final Inspection8/26/20048/27/20048/26/2004 1:58:17 PMPCANC
This is Robs cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
FIR04-00250 INSP-Conference8/26/20048/27/20048/26/2004 1:31:23 PMPCANC
This is Robs Cell number; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley