Inspections for the day of: Monday, August 27, 2007.
Number of inspections: 15
Percentage of inspections complete: 93 %
Percentage of inspections not complete: 7 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02347 Extend Permit 180 days8/20/20078/20/2007 P 
FIR07-00474 INSP-Final Inspection8/27/20078/27/20078/28/2007 11:16:30 AMPPASS
Corrections are complete, fire sprinkler permit finaled.
FIR07-00441 INSP-Alarm Testing8/21/20078/27/20078/27/2007 5:23:29 PMAFAIL
See approved plans for areas inspected today, noted one H/S is blocked, one incorrect cd rating, switched address on the sprinkler PIV and forward flow tampers.
BLD06-02000 FIRE-Final Inspection8/27/20078/27/20078/27/2007 5:20:58 PMPPASS
Life safety inspection passed.
FIR07-00741 INSP-Final Inspection8/24/20078/27/20078/27/2007 5:18:24 PMAPASS
Hood suppression system operated correctly under test conditions.
FIR07-00205 INSP-Final Inspection8/23/20078/27/20078/27/2007 4:42:11 PMAPART
Project is not ready for final per contractor due to missing ceilings at several locations, need to complete final walk-through with provided as-built plans reflecting field modifications.
FIR06-00940 INSP-Final Inspection8/23/20078/27/20078/27/2007 4:38:31 PMAPART
Tested riser alarm and supervisory conditions, need to adjust the PIV switch, forward flow completed, project is not ready for final due to missing ceilings at several locations.
BLD07-01998 FIRE-Final Inspection8/24/20078/27/20078/27/2007 2:23:22 PMPPASS
Fire life safety is satisfactory, noted field ceiling tile and permanent door hardware to be installed prior to structural final as discussed.
BLD07-01364 FIRE-Final Inspection8/27/20078/27/20078/27/2007 1:45:47 PMPPASS
Fire life safety finaled.
FIR07-00592 INSP-Final Inspection8/27/20078/27/20078/27/2007 1:44:01 PMPPASS
Final fire sprinkler inspection passed, permit finaled.
FIR07-00658 INSP-Final Inspection8/27/20078/27/20078/27/2007 1:41:37 PMPPASS
Verified required corrections, noted changes to be made at data entry regarding descriptor for supervisory signals, inspection passed, permit finaled.
FIR07-00123 FIR-Aging Inspection8/27/20078/27/20078/27/2007 11:00:21 AM DEFR
FIR07-00474 INSP-Final Inspection8/27/20078/27/20078/27/2007 10:49:14 AMPFAIL
Corrections are not complete, one head location is overspaced from an adjacent wall.
BLD07-02305 FIRE-Final Inspection8/24/20078/27/20078/27/2007 10:39:06 AMAPASS
Life safety inspection completed satisfactory.
FIR07-00644 INSP-Sprinkler Rough-in/Hydro8/24/20078/27/20078/27/2007 10:37:24 AMAFAIL
Pendent head at the second room is overspaced.