ELE08-00655
| ELE-Aging Inspection | 8/27/2008 | 8/27/2008 | 8/28/2008 10:59:11 AM | | PART |
|
|
|
ELE08-00701
| ELE-Aging Inspection | 8/27/2008 | 8/27/2008 | 8/28/2008 10:58:50 AM | | PART |
|
|
called contr will on job for listing and request final
|
ELE08-02387
| Rough-In Permanent Service | 8/26/2008 | 8/27/2008 | 8/27/2008 3:33:34 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus called box fill nail plates, complete all makeup replace all boxes with extra broken out openings, grd for other systems, install all recess cans outdoors
|
ELE08-02390
| Electrical Rough-In | 8/27/2008 | 8/27/2008 | 8/27/2008 2:51:19 PM | P | PART |
|
|
bonding grid for fountain before pour-Rick or ###-#### Dick Phone #: ###-#### bonding for both fountains ok
|
ELE08-02388
| Temporary Service | 8/27/2008 | 8/27/2008 | 8/27/2008 2:21:18 PM | P | PASS |
|
|
###-#### Internet Inspection Request from: Todd Holbrook no esc t/s u/g new ok
|
ELE08-02389
| Electrical Rough-In | 8/27/2008 | 8/27/2008 | 8/27/2008 2:20:46 PM | P | PART |
|
|
Jack, this is the home we talked about yesterday. Thanks, Dan Phone #: ###-#### Internet Inspection Request from: Dan Rohl patio ceiling ok note could not find listing mark for spa no esc
|
ELE08-01167
| Final | 8/27/2008 | 8/27/2008 | 8/27/2008 1:22:16 PM | P | PASS |
|
|
Robert Phone #: ###-#### corr made final ok
|
ELE08-01787
| Electrical Rough-In | 8/27/2008 | 8/27/2008 | 8/27/2008 12:13:03 PM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/27/2008 at 7:10:39 AM. Contact: ###-####. called left message do not know what they want inspected contr has not called me back with info
|
ELE08-02212
| Temporary Service | 8/27/2008 | 8/27/2008 | 8/27/2008 11:35:31 AM | A | FAIL |
|
|
Contact is Andy. Phone #: ###-#### Internet Inspection Request from: David Bonner corr called needs grd rods at trailer p/s 250.32, 110.3(B) & 314.3 bond bushings for metallic fittings at non-metallic box , 314.28 jbox trailer too small for straight through pull with splices, use listed for grding or plastic conn for GEC
|
ELE08-02309
| Final | 8/27/2008 | 8/27/2008 | 8/27/2008 10:22:59 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: PAT MILLER ok
|
ELE08-02065
| Permanent Service | 8/26/2008 | 8/27/2008 | 8/27/2008 9:38:52 AM | A | PASS |
|
|
We completed the power connection to the power pedestal. Phone #: ###-#### Internet Inspection Request from: Clint Tate p/s u/g new ok
|
ELE08-02065
| Final | 8/27/2008 | 8/27/2008 | 8/27/2008 9:38:34 AM | A | PASS |
|
|
We completed the power connection to the power pedestal. Phone #: ###-#### Internet Inspection Request from: Clint Tate called needs green jumper between neutral and equip grd bus
|
ELE08-02051
| Permanent Service | 8/26/2008 | 8/27/2008 | 8/27/2008 9:37:38 AM | A | PASS |
|
|
We completed the power connection to the power pedestal. Phone #: ###-#### Internet Inspection Request from: Clint Tate p/s u/g new ok
|
ELE08-02051
| Final | 8/27/2008 | 8/27/2008 | 8/27/2008 9:37:19 AM | A | PASS |
|
|
We completed the power connection to the power pedestal. Phone #: ###-#### Internet Inspection Request from: Clint Tate called needs green jumper between neutral and equip grd bus
|
ELE08-00933
| Final | 8/26/2008 | 8/27/2008 | 8/27/2008 8:33:46 AM | A | PASS |
|
|
Alan Phone #: ###-#### OK no card
|
ELE08-00932
| Final | 8/26/2008 | 8/27/2008 | 8/27/2008 8:33:13 AM | A | PASS |
|
|
Alan Phone #: ###-#### OK NO CARD
|
ELE08-00931
| Final | 8/26/2008 | 8/27/2008 | 8/27/2008 8:32:52 AM | A | PASS |
|
|
Alan Phone #: ###-#### OK NO CARD
|
ELE08-02120
| Final | 8/27/2008 | 8/27/2008 | 8/27/2008 7:32:02 AM | P | CANC |
|
|
rough in chris is contact his number is###-#### Phone #: ###-#### Internet Inspection Request from: Shawna Gates Inspection cancelled from web by: Shawna Gates
|
ELE08-02371
| Temporary Service | 8/26/2008 | 8/27/2008 | 8/27/2008 12:00:00 AM | A | CANC |
|
|
TEMP Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe
|
ELE08-02372
| Temporary Service | 8/26/2008 | 8/27/2008 | 8/26/2008 9:54:30 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Bob Glenn Inspection cancelled from web by: Bob Glenn
|