Inspections for the day of: Wednesday, August 27, 2008.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00655 ELE-Aging Inspection8/27/20088/27/20088/28/2008 10:59:11 AM PART
ELE08-00701 ELE-Aging Inspection8/27/20088/27/20088/28/2008 10:58:50 AM PART
called contr will on job for listing and request final
ELE08-02387 Rough-In Permanent Service8/26/20088/27/20088/27/2008 3:33:34 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Surerus called box fill nail plates, complete all makeup replace all boxes with extra broken out openings, grd for other systems, install all recess cans outdoors
ELE08-02390 Electrical Rough-In8/27/20088/27/20088/27/2008 2:51:19 PMPPART
bonding grid for fountain before pour-Rick or ###-#### Dick Phone #: ###-####
bonding for both fountains ok
ELE08-02388 Temporary Service8/27/20088/27/20088/27/2008 2:21:18 PMPPASS
###-#### Internet Inspection Request from: Todd Holbrook no esc t/s u/g new ok
ELE08-02389 Electrical Rough-In8/27/20088/27/20088/27/2008 2:20:46 PMPPART
Jack, this is the home we talked about yesterday.
Thanks, Dan Phone #: ###-#### Internet Inspection Request from: Dan Rohl
patio ceiling ok note could not find listing mark for spa no esc
ELE08-01167 Final8/27/20088/27/20088/27/2008 1:22:16 PMPPASS
Robert Phone #: ###-#### corr made final ok
ELE08-01787 Electrical Rough-In8/27/20088/27/20088/27/2008 12:13:03 PMAFAIL
Scheduled by a contractor via Hello! on 8/27/2008 at 7:10:39 AM. Contact: ###-####. called left message do not know what they want inspected contr has not called me back with info
ELE08-02212 Temporary Service8/27/20088/27/20088/27/2008 11:35:31 AMAFAIL
Contact is Andy. Phone #: ###-#### Internet Inspection Request from: David Bonner corr called needs grd rods at trailer p/s 250.32, 110.3(B) & 314.3 bond bushings for metallic fittings at non-metallic box , 314.28 jbox trailer too small for straight through pull with splices, use listed for grding or plastic conn for GEC
ELE08-02309 Final8/27/20088/27/20088/27/2008 10:22:59 AMAPASS
Phone #: ###-#### Internet Inspection Request from: PAT MILLER ok
ELE08-02065 Permanent Service8/26/20088/27/20088/27/2008 9:38:52 AMAPASS
We completed the power connection to the power pedestal. Phone #: ###-#### Internet Inspection Request from: Clint Tate
p/s u/g new ok
ELE08-02065 Final8/27/20088/27/20088/27/2008 9:38:34 AMAPASS
We completed the power connection to the power pedestal. Phone #: ###-#### Internet Inspection Request from: Clint Tate called needs green jumper between neutral and equip grd bus
ELE08-02051 Permanent Service8/26/20088/27/20088/27/2008 9:37:38 AMAPASS
We completed the power connection to the power pedestal. Phone #: ###-#### Internet Inspection Request from: Clint Tate
p/s u/g new ok
ELE08-02051 Final8/27/20088/27/20088/27/2008 9:37:19 AMAPASS
We completed the power connection to the power pedestal. Phone #: ###-#### Internet Inspection Request from: Clint Tate called needs green jumper between neutral and equip grd bus
ELE08-00933 Final8/26/20088/27/20088/27/2008 8:33:46 AMAPASS
Alan Phone #: ###-#### OK no card
ELE08-00932 Final8/26/20088/27/20088/27/2008 8:33:13 AMAPASS
Alan Phone #: ###-#### OK NO CARD
ELE08-00931 Final8/26/20088/27/20088/27/2008 8:32:52 AMAPASS
Alan Phone #: ###-#### OK NO CARD
ELE08-02120 Final8/27/20088/27/20088/27/2008 7:32:02 AMPCANC
rough in chris is contact his number is###-#### Phone #: ###-#### Internet Inspection Request from: Shawna Gates Inspection cancelled from web by: Shawna Gates
ELE08-02371 Temporary Service8/26/20088/27/20088/27/2008 12:00:00 AMACANC
TEMP Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe
ELE08-02372 Temporary Service8/26/20088/27/20088/26/2008 9:54:30 AMACANC
Phone #: ###-#### Internet Inspection Request from: Bob Glenn Inspection cancelled from web by: Bob Glenn