Inspections for the day of: Wednesday, August 27, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-01091 FIRE-Final Inspection8/27/20088/27/20088/27/2008 4:57:56 PMPPASS
Life safety final passed per inspection notes-see activity completed 5/2.
BLD05-01094 FIRE-Final Inspection8/27/20088/27/20088/27/2008 4:53:01 PMPPASS
Fire life safety inspection complete.
FIR08-00567 INSP-Sprinkler Rough-in8/27/20088/27/20088/27/2008 4:50:27 PMPPART
Locations on approved plan marked okayed with today's date including the restrooms and storage closet. Approved installation at the men's restroom and adjacent mech. closet only, womens restroom is not yet complete (in Grape Escape tenat space).
FIR08-00539 INSP-Sprinkler Rough-in8/27/20088/27/20088/27/2008 2:50:52 PMPPART
Field adjustments in final head location are satisfactory, rough-in at the grid ceilings is approved for cover.
FIR08-00545 INSP-Sprinkler Rough-in/Hydro8/27/20088/27/20088/27/2008 2:42:16 PMPPART
Approved installation at the men's restroom and adjacent mech. closet only, womens restroom is not yet complete (in Grape Escape tenat space - see subsequently created FIR08-00567 for further details).
FIR08-00345 FIR-Aging Inspection8/27/20088/27/20088/27/2008 2:39:01 PM DONE
Need site inspection request for permit final.
FIR08-00517 INSP-Sprinkler Rough-in/Hydro8/26/20088/27/20088/27/2008 2:37:16 PMAPART
Okayed work above sheetrock ceilings and soffits for the 6th floor-noted three heads in hard lids not yet finished, piping to be installed per plan at grid ceilings.
FIR08-00588 INSP-Final Inspection8/22/20088/27/20088/27/2008 1:18:00 PMAPART
Overhead fire sprinkler system modifications at the tenant improvement area are good for cover with the exception of the conference room and east side of the waiting area. One head added due to overspacing is not yet installed, conference room head needs to be piped separately as the number of sprinklers fed from a 1" line is exceeded.
FIR08-00289 INSP-Sprinkler Rough-in/Hydro8/27/20088/27/20088/27/2008 1:13:20 PMAPART
See stamped plan set for locations inspected and okayed for cover.
BLD08-01512 FIRE-Final Inspection8/27/20088/27/20088/27/2008 1:12:25 PMAPASS
Fire life safety passed inspection.