Inspections for the day of: Friday, August 27, 2010.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00202 INSP-Final Inspection8/24/20108/27/20108/27/2010 3:49:17 PMAFAIL
The facp and dialer were verified. But inspection was stopped after it was found that instead of just monitor modules being installed at all of the existing duct smoke detectors, new duct smoke detectors had been installed which are being powered from the facp. Also duct smoke detectors are being used for the control of what appear to be fire/smoke dampers.
FIR10-00407 INSP-Sprinkler Rough-in8/26/20108/27/20108/27/2010 3:37:08 PMAPASS
The 5' underground supply piping stub out is ok for cover.
FIR10-00330 INSP-Final Inspection8/25/20108/27/20108/27/2010 9:39:46 AMAFAIL
Provide map at the facp and provide supervisory signal as discussed due to the existing panel being capable of this output to the monitoring station.
FIR10-00328 INSP-Final Inspection8/25/20108/27/20108/27/2010 9:38:35 AMAPASS
Permit finaled