BLD11-02613
| FIRE-Final Inspection | 8/27/2012 | 8/27/2012 | 8/27/2012 3:59:50 PM | P | PASS |
|
|
Life safety passed. The lever hardware for the west exit door and the building address to be installed prior to the building inspection.
|
FIR11-00543
| INSP-Supply line flush | 8/27/2012 | 8/27/2012 | 8/27/2012 3:58:06 PM | P | PASS |
|
|
The forward flow test passed.
|
BLD12-01752
| FIRE-Final Inspection | 8/27/2012 | 8/27/2012 | 8/27/2012 3:56:06 PM | P | FAIL |
|
|
No city approved plans on site for the inspection. I noted that the exit sign and emergency lights functioned and the fire extinguisher was placed.
|
FIR12-00373
| INSP-Alarm Testing | 8/27/2012 | 8/27/2012 | 8/27/2012 3:54:24 PM | P | FAIL |
|
|
One of the two strobes needed the candella increased to meet code while I waited. When the manual pull station was activated the horn strobes did not activate. Inspection failed. Also need updated as-builts showing the relocated strobe and the one with the increased candella.
|
BLD12-01039
| FIRE-Final Inspection | 8/27/2012 | 8/27/2012 | 8/27/2012 3:51:55 PM | P | PASS |
|
|
life safety passed
|
FIR12-00285
| INSP-Final Inspection | 8/27/2012 | 8/27/2012 | 8/27/2012 2:03:31 PM | P | PASS |
|
|
Permit finaled. The hydro test and head change out will be addressed under the tenant permit.
|
FIR12-00351
| INSP-Final Inspection | 8/24/2012 | 8/27/2012 | 8/27/2012 11:11:45 AM | A | PASS |
|
|
Permit finaled. Colton was going to return with the correct size batteries. The additional tamper switches to be shown on the tenant built out fire alarm drawings.
|
BLD12-00851
| FIRE-Final Inspection | 8/24/2012 | 8/27/2012 | 8/27/2012 8:57:50 AM | A | FAIL |
|
|
I left message on the contacts voice mail and also met the electrician for testing of the smoke evac system but the project was locked with no access. No inspection was performed.
|