ELE09-02259
| ELE-Aging Inspection | 8/27/2014 | 8/27/2014 | 8/28/2014 3:24:24 PM | | DONE |
|
|
too busy
|
ELE10-01957
| ELE-Aging Inspection | 8/27/2014 | 8/27/2014 | 8/28/2014 3:22:15 PM | | DONE |
|
|
too busy
|
ELE14-01448
| Electrical Rough-In | 8/27/2014 | 8/27/2014 | 8/28/2014 8:34:18 AM | P | PASS |
|
|
Levi. Ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy ceilings ok except for 515,518 and 520
|
ELE10-01260
| Final | 8/27/2014 | 8/27/2014 | 8/27/2014 4:34:01 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Erick Baker final ok
|
ELE14-01597
| Electrical Rough-In | 8/26/2014 | 8/27/2014 | 8/27/2014 4:00:12 PM | P | PASS |
|
|
Walls, Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Mike Basye r/i walls ok dentist office whole 1st floor
|
ELE14-02370
| Rough-In Permanent Service | 8/27/2014 | 8/27/2014 | 8/27/2014 3:10:10 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt r/i ok p/s o/h n ok
|
ELE14-02376
| Temporary Service | 8/27/2014 | 8/27/2014 | 8/27/2014 2:34:44 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI grounding electrode not connected ,pole laying upside down on ground from hill
|
ELE14-01029
| Final | 8/27/2014 | 8/27/2014 | 8/27/2014 2:16:23 PM | P | FAIL |
|
|
Jay Phone #: ###-#### 210.8-GFCI protection required for garage door openers receptacles
|
ELE14-02367
| Electrical Rough-In | 8/26/2014 | 8/27/2014 | 8/27/2014 1:17:30 PM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson needed r/i p/s
|
ELE14-02367
| Rough-In Permanent Service | 8/27/2014 | 8/27/2014 | 8/27/2014 1:16:56 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson ri ok p/s u/g n ok
|
ELE14-02368
| Final | 8/26/2014 | 8/27/2014 | 8/27/2014 12:14:04 PM | A | FAIL |
|
|
Temp power pole inspection Phone #: ###-#### Inspection requested via web by Darrel Kubik 6x6 post required for o/h temp. poles. grounding electrode not connected to ground rod, u/g conduit needs to be sch 80
|
ELE14-02350
| Permanent Service | 8/25/2014 | 8/27/2014 | 8/27/2014 11:48:51 AM | A | PASS |
|
|
If possible late in the morning. Phone #: ###-#### Inspection requested via web by Brad Girard p/s o/h rec ok
|
ELE14-00644
| Final | 8/26/2014 | 8/27/2014 | 8/27/2014 11:28:46 AM | A | FAIL |
|
|
Contact is Jim Snodgrass Phone #: ###-#### Inspection requested via web by Todd Sellman u.ground UF never inspected from pull boxes to post lights. UF approx. 12" deep needs GFCI protection.
|
ELE14-02195
| Electrical Rough-In | 8/26/2014 | 8/27/2014 | 8/27/2014 11:01:07 AM | A | PASS |
|
|
This inspection will be for repairing of the wiring for the cooler in the basement. Please contact Kyle Dillon at ###-####. Thank you and have a great day! Phone #: ###-#### Inspection requested via web by Laura Longshaw r/i ok need disconnect at c/u and label panel before final
|
ELE14-00157
| Electrical Rough-In | 8/26/2014 | 8/27/2014 | 8/27/2014 10:09:30 AM | A | PASS |
|
|
Inspection for Rough-In on the 3rd floor. Contact - Craig Timmons Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok 3rd floor apts. and both stairwells and 4th floor east exterior wall only
|