Inspections for the day of: Wednesday, August 27, 2014.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-02444 FIRE-Final Inspection8/27/20148/27/20148/28/2014 11:40:11 AMPPASS
Life safety inspection passed.
BLD14-02122 FIRE-Final Inspection8/27/20148/27/20148/28/2014 11:39:42 AMPPASS
Fire life safety inspection completed and passed.
FIR14-00608 INSP-Final Inspection8/26/20148/27/20148/28/2014 11:38:58 AMPPASS
Fire alarm work tested satisfactory. Permit final approved.
FIR14-00246 INSP-Final Inspection8/26/20148/27/20148/27/2014 2:36:18 PMAFAIL
Items noted include; netcon of 7 at the time of inspection, need to provide addtional notification at some areas on the 3rd and 2nd floors, relocate MP at the 3rd floor NE exit, verify sync between EST and system sensor brand notification devices in suite 275. Provide a plan modification for resubmittal to include all field changes such as added power supplies, added SD, matrix change for deletion of elevator recall, correct zones at panel, added notification devices throughout all three floor levels, floorplan changes, etc. Approved plan set to match field install.
BLD14-00518 FIRE-Final Inspection8/26/20148/27/20148/27/2014 11:32:47 AMAPASS
Fire life safety final approved.
FIR14-00527 INSP-Sprinkler Rough-in8/26/20148/27/20148/27/2014 11:32:10 AMAPART
Okayed for ceiling cover at the sheetrock lid as marked and dated on approved plans.
FIR14-00615 INSP-Sprinkler Rough-in8/26/20148/27/20148/27/2014 11:16:45 AMAPART
Fire sprinkler work okay for cover at the remodel area per the permit scope. Final pending ceiling tile and escutcheons throughout.
BLD14-00769 FIRE-Final Inspection8/26/20148/27/20148/27/2014 10:42:40 AMAPASS
Fire life safety passed.
FIR14-00451 INSP-Final Inspection8/27/20148/27/20148/27/2014 9:12:32 AMACANC
Please call 30 min prior to arrival...... Phone #: ###-#### >> Inspection requested via web by Jeff Walton Inspection cancelled from web by: Jeff Walton