BLD15-02411
| FIRE-Final Inspection | 8/26/2015 | 8/27/2015 | 8/27/2015 12:18:31 PM | A | FAIL |
|
|
No FIR permit associated with this project at time of inspection, specified in Plan Review notes that a fire alarm permit will be required for project. The fire alarm panel was in alarm at time of inspection, repairs/modifications/additions to current fire alarm system are required, informed POC Lori, phone ###-#### to contact a fire alarm contractor to have system updated/repaired before life fire safety can be completed. Egress discharge area located on west side did not have exterior egress illumination, needs to be corrected before next inspection.
|
FIR15-00493
| INSP-Sprinkler Rough-in/Hydro | 8/26/2015 | 8/27/2015 | 8/27/2015 11:43:30 AM | A | PART |
|
|
Hydrostatic test passed/complete on dry system. 24 hour air test started at 1140, 43psi at test start time.
|
BLD15-01208
| FIRE-Final Inspection | 8/26/2015 | 8/27/2015 | 8/27/2015 9:47:15 AM | A | PASS |
|
|
Life fire safety passed/complete
|
FIR14-00875
| INSP-Final Inspection | 8/26/2015 | 8/27/2015 | 8/26/2015 2:04:18 PM | A | CANC |
|
|
>> Inspection requested via mobile web by Nathan Proce Inspection cancelled via mobile web on Wednesday, August 26, 2015.
|