Inspections for the day of: Tuesday, August 27, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03215 Electrical Rough-In8/27/20198/27/20198/27/2019 2:36:26 PMPPART
Please call 30 mins prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Warned not to cover in ant way prior to inspection.
All bathroom walls not ready, rest of walls rough in ok cover
ELE19-03174 Electrical Rough-In8/27/20198/27/20198/27/2019 1:58:02 PMPPART
Please call Mike Inspection requested via web by Kevin Perez
Exterior of outer wall only, and more kitchen walls as noted on contractor print rough in ok cover.
ELE19-03143 Rough-In Permanent Service8/26/20198/27/20198/27/2019 1:17:24 PMPPASS
Inspection requested via web by ERIC CENTERS
Rough in ok cover p/s u/g n ok
ELE19-03203 Rough-In Permanent Service8/26/20198/27/20198/27/2019 11:00:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Ryan Wilson
Rough in ok cover
ELE19-02502 Final8/26/20198/27/20198/27/2019 10:28:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Ryan Wilson Final ok
ELE19-02028 Electrical Rough-In8/27/20198/27/20198/27/2019 10:00:11 AMPCANC
Please call 30 mins prior Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
ELE19-03197 Temporary Service8/26/20198/27/20198/27/2019 9:40:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Robert Murray
Temp pole laying on ground next to transformer. t/s u/g n ok
ELE19-03198 Electrical Rough-In8/26/20198/27/20198/27/2019 9:25:04 AMAFAIL
Walls are ready for rough in inspection. Front door is open. Thank You Phone #: ###-#### Inspection requested via web by Kelly Felin
300.21- Penetration in 2 hr fire wall shall be maintained. Low volt shall be installed in a 2 hr rated box, and repair round holes in upper wall to maintain 2 hr rated wall as per BLD permit.
300.4- Raceways and cables shall not be installed with in 1 1/4" of framing surface. '
330.12- MC cable shall not be installed where subfect to damage. Do not secure on interior of 2x4 studs.