ELE19-03215
| Electrical Rough-In | 8/27/2019 | 8/27/2019 | 8/27/2019 2:36:26 PM | P | PART |
|
|
Please call 30 mins prior Phone #: ###-#### Inspection requested via web by Kerri Hamilton Warned not to cover in ant way prior to inspection. All bathroom walls not ready, rest of walls rough in ok cover
|
ELE19-03174
| Electrical Rough-In | 8/27/2019 | 8/27/2019 | 8/27/2019 1:58:02 PM | P | PART |
|
|
Please call Mike Inspection requested via web by Kevin Perez Exterior of outer wall only, and more kitchen walls as noted on contractor print rough in ok cover.
|
ELE19-03143
| Rough-In Permanent Service | 8/26/2019 | 8/27/2019 | 8/27/2019 1:17:24 PM | P | PASS |
|
|
Inspection requested via web by ERIC CENTERS Rough in ok cover p/s u/g n ok
|
ELE19-03203
| Rough-In Permanent Service | 8/26/2019 | 8/27/2019 | 8/27/2019 11:00:40 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Rough in ok cover
|
ELE19-02502
| Final | 8/26/2019 | 8/27/2019 | 8/27/2019 10:28:54 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Final ok
|
ELE19-02028
| Electrical Rough-In | 8/27/2019 | 8/27/2019 | 8/27/2019 10:00:11 AM | P | CANC |
|
|
Please call 30 mins prior Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
ELE19-03197
| Temporary Service | 8/26/2019 | 8/27/2019 | 8/27/2019 9:40:11 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Robert Murray Temp pole laying on ground next to transformer. t/s u/g n ok
|
ELE19-03198
| Electrical Rough-In | 8/26/2019 | 8/27/2019 | 8/27/2019 9:25:04 AM | A | FAIL |
|
|
Walls are ready for rough in inspection. Front door is open. Thank You Phone #: ###-#### Inspection requested via web by Kelly Felin 300.21- Penetration in 2 hr fire wall shall be maintained. Low volt shall be installed in a 2 hr rated box, and repair round holes in upper wall to maintain 2 hr rated wall as per BLD permit. 300.4- Raceways and cables shall not be installed with in 1 1/4" of framing surface. ' 330.12- MC cable shall not be installed where subfect to damage. Do not secure on interior of 2x4 studs.
|