MEC19-02974
| Final | 8/26/2019 | 8/27/2019 | 8/27/2019 3:50:03 PM | P | NR |
|
|
VINNIE ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- per Mike general contractor debating on vented or unvented sofitt above fireplace thimble or moving thimble down 3"- will call in when issue has been corrected
|
MEC19-03783
| Pressure Test | 8/27/2019 | 8/27/2019 | 8/27/2019 3:14:06 PM | P | PASS |
|
|
Oleg Phone #: ###-####- 20lb gas pass tagged meter location- 5lb flue pass
|
MEC19-03783
| Rough-in | 8/27/2019 | 8/27/2019 | 8/27/2019 3:13:36 PM | P | FAIL |
|
|
Oleg Phone #: ###-####- need 1" clearance on b vent 2nd floor attic- need to replace smashed 4" dryer duct and fitting at attic- flex ducting needs to be installed per manufacture installation instructions- mantel installed needs moved up 1" per installation instructions and measurement is from top of appliance not deflector- see correction notice front entry window
|
MEC19-03418
| Final | 8/23/2019 | 8/27/2019 | 8/27/2019 2:08:08 PM | P | PASS |
|
|
Call Robert in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout- a/c coil co ok
|
MEC19-03825
| Final | 8/26/2019 | 8/27/2019 | 8/27/2019 1:11:26 PM | P | NH |
|
|
Phone #: ###-#### Inspection requested via web by Denise Colin- no one home- no access- rang doorbell twice and knocked
|
MEC19-03616
| Final | 8/26/2019 | 8/27/2019 | 8/27/2019 1:01:49 PM | P | PASS |
|
|
Please inspect from 12-4. Contact is Brandon Cox ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
|
MEC19-03652
| Conference | 8/26/2019 | 8/27/2019 | 8/27/2019 11:09:21 AM | A | DONE |
|
|
consult with Luke Phone #: ###-#### Inspection requested via web by Brandon Sorensen- went over class 1 hood- since no labeling can be found on ul listed hood by captive aire will install to 2012 IMC-
|
MEC19-03637
| Rough-in | 8/26/2019 | 8/27/2019 | 8/27/2019 10:40:08 AM | A | PASS |
|
|
inspection is for line set and condensate drain from coil Phone #: ###-#### Inspection requested via web by Joseph Profitt
|
MEC19-03637
| Pressure Test | 8/26/2019 | 8/27/2019 | 8/27/2019 10:39:56 AM | A | PASS |
|
|
underground gas line Phone #: ###-#### Inspection requested via web by Joseph Profitt- 20lb gas pass- ok to back fill- tagged meter location
|
MEC19-02049
| Rough-in | 8/26/2019 | 8/27/2019 | 8/27/2019 10:39:25 AM | A | PASS |
|
|
sealer inspection Phone #: ###-#### Inspection requested via web by Brandon Sorensen- seal on all ducting complete- ok to insulate all remaining ducts- ok for grid- call in when registers and insulation completed
|
MEC19-03639
| Rough-in | 8/26/2019 | 8/27/2019 | 8/27/2019 10:21:55 AM | A | PASS |
|
|
inspection is for line set and condensate drain from coil Phone #: ###-#### Inspection requested via web by Joseph Profitt- R/I ok- need to support all lineset under mobile home by final
|
MEC19-03639
| Pressure Test | 8/26/2019 | 8/27/2019 | 8/27/2019 10:21:22 AM | A | PASS |
|
|
underground gas line Phone #: ###-#### Inspection requested via web by Joseph Profitt- 20lb gas pass- underground gas piping ok to back fill- tagged meter location
|
MEC19-03641
| Rough-in | 8/26/2019 | 8/27/2019 | 8/27/2019 10:15:06 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Joseph Profitt- R/I ok
|
MEC19-03641
| Pressure Test | 8/26/2019 | 8/27/2019 | 8/27/2019 10:14:46 AM | A | PASS |
|
|
underground gas line Phone #: ###-#### Inspection requested via web by Joseph Profitt- 20lb gas pass- underground gas piping ok to back fill
|
MEC19-03443
| Rough-in | 8/26/2019 | 8/27/2019 | 8/27/2019 9:45:06 AM | A | PASS |
|
|
AUSTIN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- 60lb gas test whole system from kitchen to roof ok- need documentation from engineer stating ok to use compression fitting for tie in on existing line since upgrading to 5lb system and have onsite to view by final
|
MEC19-03513
| Final | 8/26/2019 | 8/27/2019 | 8/27/2019 9:19:56 AM | A | PASS |
|
|
MORNING INSPECTION REQUESTED.. PLEASE CALL CUSTOMER SO HE CAN MEET YOU THERE. BEFORE YOU HEAD OUT. Phone #: ###-#### Inspection requested via web by Trina DeBoard- furnace a/c coil gas piping co ok
|
MEC19-03822
| Final | 8/26/2019 | 8/27/2019 | 8/27/2019 9:13:30 AM | A | PASS |
|
|
final - call brandon Phone #: ###-#### Inspection requested via web by Brandon Sorensen- Relocation 2 sidewall exhaust fans from existing build to new building ok
|
MEC19-03751
| Final | 8/22/2019 | 8/27/2019 | 8/27/2019 8:45:09 AM | A | PASS |
|
|
Please call Rick Price prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co ok
|
MEC19-03738
| Rough-in | 8/26/2019 | 8/27/2019 | 8/27/2019 8:37:20 AM | A | PASS |
|
|
Matt Phone #: ###-####
|
MEC19-02356
| Final | 8/23/2019 | 8/27/2019 | 8/27/2019 8:21:38 AM | A | PASS |
|
|
Homeowner requests the inspection be done between 8-10am. Please call if that cannot be accommodated: Tony ###-#### Phone #: ###-#### Inspection requested via web by Michael Stimpson- furnace a/c coil co ok
|
MEC19-00220
| Mec-Aging Inspection | 8/27/2019 | 8/27/2019 | 8/27/2019 7:44:25 AM | | FAIL |
|
|
needs called in for inspection- if no activity will expire permit permit next aging
|
MEC19-00266
| Mec-Aging Inspection | 8/27/2019 | 8/27/2019 | 8/27/2019 7:42:30 AM | | CANC |
|
|
needs called in for inspection when ready- WIP
|
MEC17-03568
| Mec-Aging Inspection | 8/27/2019 | 8/27/2019 | 8/27/2019 7:41:47 AM | | CANC |
|
|
needs called in for inspection- reopened permit
|