Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03180 Rough-In Permanent Service8/27/20198/27/20198/27/2019 3:37:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Cevyn Recla
Rough-in ok to cover
p/s o/h n ok
ELE19-03207 Final8/27/20198/27/20198/27/2019 2:26:18 PMPCANC
The service was replaced after being damaged by a falling tree. Replaced existing. Homeowner has dog tied up in backyard. Please call 30 minutes ahead of time and I will try to meet you on site or answer any questions. Phone #: ###-#### Inspection requested via web by Casey Fouts
No final, need to verify grounding source or add additional ground rods as needed, grounding electrode was tied into existing ground conductors that goees into concrete on patio, Contractor will prove weither it is a contrete ecased or will drive 2 ground rods
ELE19-03207 Permanent Service8/27/20198/27/20198/27/2019 2:26:02 PMPPASS
The service was replaced after being damaged by a falling tree. Replaced existing. Homeowner has dog tied up in backyard. Please call 30 minutes ahead of time and I will try to meet you on site or answer any questions. Phone #: ###-#### Inspection requested via web by Casey Fouts
p/s o/h rec ok-IDPCO energized proir to inspections refer to nots on final fro requirements
ELE19-02156 Final8/27/20198/27/20198/27/2019 1:23:51 PMPPASS
Contact Josh Slater
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Final ok
ELE18-02854 Final8/27/20198/27/20198/27/2019 12:05:53 PMPPASS
Final at Building H. Phone #: ###-#### Inspection requested via web by Scott Wilson
Bld H final ok
Card signed
ELE18-03385 Electrical Rough-In8/27/20198/27/20198/27/2019 12:05:25 PMAPASS
Building J partial final in units 100, 101, 102, 103, 200, 201, 202, 203, 300, 301, 302, 303 Phone #: ###-#### Inspection requested via web by Scott Wilson
Units as requested checked out and are fine
ELE19-03202 Permanent Service8/26/20198/27/20198/27/2019 12:04:22 PMAPASS
took down exiting service so that rotted wood could be fixed and rehung service Phone #: ###-#### Inspection requested via web by Chris Berthelot
p/s o/h rec ok
ELE19-03169 Electrical Rough-In8/26/20198/27/20198/27/2019 9:56:57 AMAPASS
Pls contact Bryce (Foreman) @ ###-#### or Barry (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes
Addition of solar panels and changing of disc to handle 35 amps ok
ELE19-03169 Final8/27/20198/27/20198/27/2019 9:56:50 AMPPASS
Pls contact Bryce (Foreman) @ ###-#### or Barry (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes
Solar Array addition final ok