Inspections for the day of: Tuesday, August 27, 2019.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03573 Final8/27/20198/27/20198/27/2019 4:06:33 PMPPART
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- only three units are finished at this time
units 3,6,7 furnace ac coil ok
MEC19-03288 Pressure Test8/26/20198/27/20198/27/2019 3:27:26 PMAPASS
Please call Larry prior to heading out to ensure on pressure. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- 5lb flue pressure test ok
- final ok
MEC19-01675 Final8/26/20198/27/20198/27/2019 2:57:13 PMPFAIL
Field super: Jason Landers Phone #: ###-#### Inspection requested via web by Lisa Whitney
- need air balance report onsite
- duct blast sticker needs info filled out
MEC19-03134 Final8/27/20198/27/20198/27/2019 2:55:26 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace ac coil co ok
MEC19-03788 Final8/26/20198/27/20198/27/2019 2:41:34 PMPFAIL
Call HO Bill ###-#### // Phone #: ###-#### Inspection requested via web by Michael Stimpson
- need to see proper UL connectors on mc cables from the outdoor unit to the indoor units
- need to see an electricl permit updated to show new ductless split (homeowner has an electrical permit already)
- condensate line down stairs needs to be min 3/4" approved material and grade out building.
MEC19-02488 Final8/27/20198/27/20198/27/2019 2:13:19 PMPPASS
lock box code is 3380 Phone #: ###-#### Inspection requested via web by Lynn Johnston
- final ok
MEC19-03838 Final8/27/20198/27/20198/27/2019 1:25:54 PMPNH
PLEASE CALL JASON THE HOMEOWNER WHEN 30 MINS IN ROUTE. HE HAS TO PICK HIS KIDS UP FROM 315-345P- IF YOU CAN WORK AROUND THAT HE WOULD BE VERY GRATEFUL Phone #: ###-#### Inspection requested via web by Rick Montgomery
- no access left notice on front door
MEC19-03333 Final8/27/20198/27/20198/27/2019 1:09:47 PMPPASS
Call ahead to the home owner = Lester @ ###-#### Phone #: ###-#### Inspection requested via web by Angie Maguire
- final ok
MEC19-03063 Final8/27/20198/27/20198/27/2019 12:46:41 PMPPASS
this is for a business and they are open 8a-5p, just head out when your ready. I left my office number above, my name is Steve with Diamond Heating and Cooling Phone #: ###-#### Inspection requested via web by Rick Montgomery
- A/C coil ok
MEC19-02852 Rough-in8/26/20198/27/20198/27/2019 11:58:42 AMPPART
This is a rough-in for Phase 4 of the project. Please call Glen with any questions. Thank you. Phone #: ###-#### Inspection requested via web by Yvonne Bowman
- phase 4 partial R/I ok duct seal ok
- ok for insulation cover
MEC19-03806 Pressure Test8/23/20198/27/20198/27/2019 11:35:22 AMAPASS
Please contact Tom prior to arrival. Phone #: ###-#### Inspection requested via web by Jamee Shoecraft
- 20lb gas pressure test ok
- need to see an electrical permit ( homeowner said he was going to pull a homeowners permit)
MEC19-03828 Final8/26/20198/27/20198/27/2019 10:32:06 AMACANC
Please call general contractor, Joshua Jackson, ###-#### to meet you there. Phone #: ###-#### Inspection requested via web by Mary LaFayette
- rescheduled as a R/I and gave it a partial
- need to see supply under cabinet ducted out
MEC19-03828 Rough-in8/27/20198/27/20198/27/2019 10:28:29 AMAPART
Please call general contractor, Joshua Jackson, ###-#### to meet you there. Phone #: ###-#### Inspection requested via web by Mary LaFayette
- supply and return ducting relocate R/I ok
- need to see supply under kitcken cabinet ducted out
MEC19-03816 Pressure Test8/26/20198/27/20198/27/2019 9:45:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Michele Atwood
- 60lb gas pressure test ok
- backfill ok
MEC19-00346 Pressure Test8/26/20198/27/20198/27/2019 9:27:09 AMAPASS
Albert Phone #: ###-####
- 60lb gas pressure test ok
- tagged meter location
MEC19-00216 Mec-Aging Inspection8/27/20198/27/20198/27/2019 9:08:28 AM DONE
Called Contractor about their mechanical aging permit. An electrical permit still needs to be pulled for the mini split and a final inspection scheduled. Permit has not been active since Jan. 2019 and will expire at the next aging inspection if not active.
MEC19-00268 Mec-Aging Inspection8/27/20198/27/20198/27/2019 9:01:30 AM DONE
WIP
MEC19-02911 Final8/22/20198/27/20198/27/2019 8:58:33 AMAFAIL
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart
- need air balance report onsite
- water heater b vent needs supported