Inspections for the day of: Tuesday, August 28, 2001.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-00340 ELE-Aging Inspection8/28/20018/28/20018/28/2001 12:00:00 AM PASS
completed. 8/28/2001 10:11:53 AM
ELE01-01725 ELE-Aging Inspection8/28/20018/28/20018/28/2001 12:00:00 AM NR
no action 8/28/2001 10:10:11 AM
ELE01-01766 ELE-Aging Inspection8/28/20018/28/20018/28/2001 12:00:00 AM NR
no action 8/28/2001 10:11:06 AM
ELE01-03008 Electrical Rough-In8/27/20018/28/20018/28/2001 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 08/27/2001 at 12:00:52. Contact: ###-####. 2 welder plugs; completed. 8/28/2001 9:12:50 AM
ELE01-03010 Rough-In Permanent Service8/27/20018/28/20018/28/2001 12:00:00 AMAFAIL
chip ###-#### r/i & ser. nec: 331-11: pvc conduit shall be supported within 3ft of cabinet
nec: 350-18: flex metal conduit secured @intervals of 41/2ft. nec: 110-12: openings in boxes shall be closed. cables shall be inclosed in box of 1 hour fire-rated wall. 8/28/2001 11:56:00 AM
ELE01-02916 Electrical Rough-In8/27/20018/28/20018/28/2001 12:00:00 AMAPASS
###-####. p v c conduit in trench. 8/28/2001 10:39:29 AM
ELE01-02627 Final8/27/20018/28/20018/28/2001 12:00:00 AMAPASS
###-####. completedl 8/28/2001 12:28:54 PM
ELE01-00758 Final8/27/20018/28/20018/28/2001 12:00:00 AMAPASS
gate code *1114 ###-####. completed. pool and spa by different contractor. 8/28/2001 10:08:29 AM
ELE01-02980 Electrical Rough-In8/27/20018/28/20018/28/2001 12:00:00 AMAFAIL
###-#### ED. 110-12: openings shall be closed. 331-11: pvc shall be suppoted at 3ft of cabined. 350-18 flex conduit shall be supported at intervals of no more than 41/2 ft
corrections posted. 8/28/2001 12:02:57 PM
ELE01-02080 Final8/27/20018/28/20018/28/2001 12:00:00 AMPCANC
###-#### mike call first. not completed; contractor will reschedule. 8/28/2001 2:26:14 PM
ELE01-03018 Rough-In Permanent Service8/28/20018/28/20018/28/2001 12:00:00 AMPPASS
###-####. ele r/i; perm/svc.

p/s ug n rick's ele #3018-ok 8/28/2001 2:00:11 PM
ELE01-03023 Temporary Service8/28/20018/28/20018/28/2001 12:00:00 AMPPASS
roudy ###-#### t/p . temporary service.

t/s ug extreme ele #3023-ok 8/28/2001 3:02:14 PM
ELE01-03002 Final8/28/20018/28/20018/28/2001 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 08/28/2001 at 10:51:09. Contact: ###-####. inspection should ele r/i. 8/28/2001 2:40:25 PM
ELE01-02230 Final8/28/20018/28/20018/28/2001 12:00:00 AMPPASS
###-#### DL . completed 8/28/2001 3:50:20 PM
ELE01-03002 Electrical Rough-In8/28/20018/28/20018/28/2001 12:00:00 AMPPASS
Added by Inspector: 403 On 8/28/2001 2:41:20 PM garage in rear.