Inspections for the day of: Wednesday, August 28, 2002.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02228 Electrical Rough-In8/27/20028/28/20028/28/2002 12:00:00 AMAPASS
ceiling; Phone #: ###-#### ok 8/28/2002 1:05:34 PM
ELE02-02664 Electrical Rough-In8/27/20028/28/20028/28/2002 12:00:00 AMAFAIL
###-#### need to meet with contractor called bonding for spa p/s all messed up address sub panel grds and neutrals service panel altered calc service size 8/28/2002 12:29:01 PM
ELE02-02641 Electrical Rough-In8/27/20028/28/20028/28/2002 12:00:00 AMAFAIL
###-#### cor. posted 45.00 fee due same corrections PLass posted plus kitchen shall be wired too meet 2002 NEC called 8/28/2002 11:17:42 AM
ELE02-02267 Electrical Rough-In8/27/20028/28/20028/28/2002 12:00:00 AMAPASS
###-#### ok 8/28/2002 12:03:51 PM
ELE02-02654 Electrical Rough-In8/27/20028/28/20028/28/2002 12:00:00 AMAFAIL
###-#### or ###-#### cor. posted called 210.52(B)(C) remove disposal from kit circuit, box fill, free length and shall not use red wire as grd circuit for micro wave 314.43 remove screws from inside of plastic boxes 8/28/2002 12:02:36 PM
ELE02-02242 Electrical Rough-In8/27/20028/28/20028/28/2002 12:00:00 AMPPASS
ceiling insp john- ###-#### ok 8/28/2002 5:34:28 PM
ELE02-02513 Electrical Rough-In8/28/20028/28/20028/28/2002 12:00:00 AMPFAIL
wall\\###-#### cor. posted called348.30 strap flex within 12 inches of boxes,352.30 pvc within 3ft of boxes , 358.30 emt within 3ft of boxes, 300.4(A)(1)and (D) nail plates, and 11/4 inches for all flex 8/28/2002 4:27:28 PM
ELE02-02674 Electrical Rough-In8/28/20028/28/20028/28/2002 12:00:00 AMPPASS
als elec ###-#### r/i ok 8/28/2002 4:59:33 PM
ELE02-02215 Final8/28/20028/28/20028/28/2002 12:00:00 AMPPASS
call first ###-#### ok card signed 8/28/2002 6:27:57 PM