Inspections for the day of: Wednesday, August 28, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00214 INSP-Alarm Testing8/27/20028/28/20028/28/2002 12:00:00 AMAFAIL
provide knox key box, provide proper orfice in the sprinkler system test line, move duct smoke detectors from the return side to the supply side, move smoke detector that is over the panel to the deck 8/28/2002 9:33:30 AM
BLD02-00964 FIRE-Final Inspection8/27/20028/28/20028/28/2002 12:00:00 AMAFAIL
provide fire extinguisher, lock on the restroom door locks people in so it needs changed, door hardware on storage room needs to be changed to approved type, provide approved plans on site so I can finish the inspection 8/28/2002 10:55:24 AM
FIR02-00284 INSP-Supply line flush8/27/20028/28/20028/28/2002 12:00:00 AMPPART
upstairs sprinkler heads are OK but the piping still needs eq bracing and retaining straps. The down stairs main reroute looks ok but needs EQ bracing, one head needs to be relocated between floor penatrations and sprinkler head layout will need to be verified over the new mechanical units 8/28/2002 4:50:59 PM
BLD02-01688 FIRE-Final Inspection8/28/20028/28/20028/28/2002 12:00:00 AMPPASS
fire life/safety finaled and fire sprinkler finaled 8/28/2002 2:42:44 PM