Inspections for the day of: Thursday, August 28, 2003.
Number of inspections: 19
Percentage of inspections complete: 95 %
Percentage of inspections not complete: 5 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00187 INSP-Final Inspection8/26/20038/26/2003 A 
BLD03-01636 FIRE-Sprinkler Rough-in8/27/20038/28/20038/28/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 8/27/2003 at 11:50:41 AM. Contact: ###-####. sprinklers okay to cover; need alarm plan submittals for new strobe in training room and interconnection to west building per plan review notes 8/29/2003 5:09:58 AM
FIR03-00141 INSP-Final Inspection8/28/20038/28/20038/28/2003 12:00:00 AMAPART
per Dave Miller a temp is approved for fire/life safety pending Simplex supplying as builts due to changes and providing maps of initiating devices 8/28/2003 8:59:07 AM
FIR03-00139 INSP-Sprinkler Rough-in8/27/20038/28/20038/28/2003 12:00:00 AMAPART
pipe in corridors has excessive upward movement - need to restrain; rooms okay to cover on second floor only 8/28/2003 11:03:54 AM 8/28/2003 11:05:26 AM
FIR03-00136 INSP-Sprinkler Rough-in8/27/20038/28/20038/28/2003 12:00:00 AMAPART
pipe in corridors has excessive upward movement - need to restrain; rooms okay to cover on second floor only 8/28/2003 11:04:04 AM 8/28/2003 11:05:05 AM
FIR03-00137 INSP-Sprinkler Rough-in8/27/20038/28/20038/28/2003 12:00:00 AMAPART
pipe in corridors has excessive upward movement - need to restrain; rooms okay to cover on second floor only 8/28/2003 11:04:10 AM 8/28/2003 11:05:16 AM
FIR03-00135 INSP-Sprinkler Rough-in8/27/20038/28/20038/28/2003 12:00:00 AMAPART
pipe in corridors has excessive upward movement - need to restrain; rooms okay to cover on second floor only 8/28/2003 11:04:19 AM 8/28/2003 11:05:39 AM
FIR03-00115 INSP-Sprinkler Rough-in8/27/20038/28/20038/28/2003 12:00:00 AMAPART
pipe in corridors has excessive upward movement - need to restrain; rooms okay to cover on second floor only 8/28/2003 11:04:25 AM 8/28/2003 11:05:51 AM
FIR03-00138 INSP-Sprinkler Rough-in8/27/20038/28/20038/28/2003 12:00:00 AMAPART
pipe in corridors has excessive upward movement - need to restrain; rooms okay to cover on second floor only 8/28/2003 11:04:32 AM 8/28/2003 11:06:00 AM
FIR03-00069 INSP-Sprinkler Rough-in/Hydro8/27/20038/28/20038/28/2003 12:00:00 AMAPASS
UG hydro okay - still need to flush 8/28/2003 10:57:22 AM
BLD02-02863 FIRE-Final Inspection8/27/20038/28/20038/28/2003 12:00:00 AMAPART
temp occupancy is approved per Dave Miller for fire/life safety pending Simplex providing fire alarm as builts and map of initiating devices 8/28/2003 9:00:21 AM
FIR03-00378 INSP-Final Inspection8/27/20038/28/20038/28/2003 12:00:00 AMAFAIL
fn ###-####- nicole sprinkler tamper not adjusted properly; sprinkler backflow cycles open and closed (Ames 2000) causing flow switch not to work 8/29/2003 5:08:36 AM
FIR03-00451 INSP-Final Inspection8/28/20038/28/20038/28/2003 12:00:00 AMPPASS
RICK ( PAGER ); Phone #: ###-#### Internet Inspection Request from: Darla Downs
FIR03-00478 INSP-Final Inspection8/28/20038/28/20038/28/2003 12:00:00 AMPPASS
FIR03-00478 INSP-Final Inspection8/28/20038/28/20038/28/2003 12:00:00 AMPPASS
FIR03-00478 INSP-Final Inspection8/28/20038/28/20038/28/2003 12:00:00 AMPPASS
FIR03-00478 INSP-Final Inspection8/28/20038/28/20038/28/2003 12:00:00 AMPPASS
BLD03-01769 FIRE-Final Inspection8/27/20038/28/20038/28/2003 12:00:00 AMPPART
JIM; Phone #: ###-#### Internet Inspection Request from: Marc Lileks per Dave Miller fire/life safety will be on temp occupancy pending approval and testing of new duct detectors for AHU shutdown 8/28/2003 1:29:52 PM
BLD03-01769 FIRE-Final Inspection8/27/20038/28/20038/28/2003 12:00:00 AMPPART
JIM; Phone #: ###-#### Internet Inspection Request from: Marc Lileks per Dave Miller fire/life safety will be on temp occupancy pending approval and testing of new duct detectors for AHU shutdown 8/28/2003 1:29:52 PM