Inspections for the day of: Monday, August 28, 2006.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01631 ELE-Aging Inspection8/28/20068/28/20069/1/2006 1:37:05 PM DONE
ELE05-02730 ELE-Aging Inspection8/28/20068/28/20068/29/2006 7:51:57 AM PART
wsuc
ELE06-03173 Rough-In Permanent Service8/28/20068/28/20068/28/2006 3:35:08 PMPPART
Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt r/i only ok corr for p/s 314.3 needs bond bushings for metal raceways in plastic jbox, 110.26(F)(2) remove a/c lines from below p/s, use plastic conn for GEC at p/s
ELE06-00554 Electrical Rough-In8/28/20068/28/20068/28/2006 2:59:54 PMPFAIL
richard ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
corr. met owner's son 300.4 nail plates 11/4", 210.52(B) address SABC, 250.148 splice all equip grds grd together at boxes 14 and 12, 110.2&3 cheetah boxes are not classed for fire, wall, or ceiling need info, 334.80 seperate cables through 1 hole above panel, talked to Tom A structural needs permit and work done too match they added a living rm and kit house now has 2 kitchens looks like they are making a aprtment out of attached garage told them to go back to plan check and resubmit
ELE06-03160 Permanent Service8/28/20068/28/20068/28/2006 1:46:54 PMPCANC
As early as possible; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen see added r/i
ELE06-03160 Electrical Rough-In8/28/20068/28/20068/28/2006 1:46:28 PMPPART
As early as possible; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen electrode ok for concrete cover only
ELE06-01274 Final8/28/20068/28/20068/28/2006 1:27:11 PMPPASS
garage code 4321; Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok
ELE06-02020 Electrical Rough-In8/28/20068/28/20068/28/2006 12:45:34 PMPPASS
eric - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
high and low voltage ok walls and ceilings
ELE06-03134 Final8/25/20068/28/20068/28/2006 12:44:42 PMAPASS
Ron Harrold ###-#### ok corrections made
ELE06-01404 Final8/25/20068/28/20068/28/2006 12:15:52 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corr. fee due 410.8 clearence closet fixtures unit 8971&75
ELE06-01401 Final8/25/20068/28/20068/28/2006 12:11:36 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corr fee due reversed polarity mech. rm
ELE06-01405 Final8/25/20068/28/20068/28/2006 12:10:05 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
ELE06-02626 Final8/25/20068/28/20068/28/2006 10:27:07 AMAPASS
Ron Harrold ###-####
ELE06-02571 Final8/25/20068/28/20068/28/2006 10:26:53 AMAPASS
Ron Harrold ###-####
ELE06-03005 Final8/25/20068/28/20068/28/2006 10:26:38 AMAPASS
Ron Harrold ###-####
ELE06-03082 Temporary Service8/24/20068/28/20068/28/2006 9:57:02 AMAPASS
Scheduled by a contractor via Hello! on 8/24/2006 at 11:00:56 AM. Contact: ###-####. t/s u/g new ok
ELE06-03083 Temporary Service8/24/20068/28/20068/28/2006 9:56:20 AMAPASS
Scheduled by a contractor via Hello! on 8/24/2006 at 11:01:31 AM. Contact: ###-####. t/su/g new ok
ELE06-03137 Permanent Service8/26/20068/28/20068/28/2006 8:35:38 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson
p/s o/h new ok
ELE06-03185 Electrical Rough-In8/25/20068/28/20068/28/2006 8:13:35 AMAPART
need inspection on U/G for cover. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH u/g inside of building and electrode ok only outside u/g shall be be 18" or under concrete called