Inspections for the day of: Tuesday, August 28, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00154 FIR-Aging Inspection8/28/20078/28/20078/30/2007 6:06:05 PM DEFR
BLD07-01999 FIRE-Final Inspection8/28/20078/28/20078/28/2007 5:19:26 PMPPASS
Fire life safety is acceptable, noted approved door hardware at the exam room to be verified by structural inspector prior to permit final.
FIR07-00743 INSP-Final Inspection8/28/20078/28/20078/28/2007 5:17:10 PMPPASS
Fire sprinkler permit finaled.
FIR07-00743 INSP-Sprinkler Rough-in8/28/20078/28/20078/28/2007 5:16:27 PMPPASS
OH sprinkler modifications are satisfactory.
FIR07-00441 INSP-Final Inspection8/27/20078/28/20078/28/2007 5:15:32 PMAFAIL
Tested remainder of devices on sheet FP2.1, noted locations on plan in need of correction including non-functional a/v devices, incorrect cd settings, blocked a/v, noted six duct detectors with the sample and vent tubes switched- need to install per mfg. recommendations or provide air flow test data.
FIR07-00712 INSP-Final Inspection8/27/20078/28/20078/28/2007 1:46:21 PMANH
Contractor was not available for an AM inspection as scheduled.
FIR07-00448 INSP-Sprinkler Rough-in8/28/20078/28/20078/28/2007 12:59:13 PMPFAIL
Provide sprinkler coverage at the second floor dormer concealed space or fill entirely with insulation, provide matching temp. sprinkler heads under the stairs at the first floor, two uprights at the attic are blocked by insulation.
FIR07-00713 INSP-Final Inspection8/28/20078/28/20078/28/2007 12:31:54 PMPDEFR
Inspection to be completed per AHJ by Deputy K. Sandahl with the office of Idaho State Fire Marshal Dept. of Insurance.
BLD06-02542 FIRE-Final Inspection8/28/20078/28/20078/28/2007 12:28:07 PMPFAIL
SD at the hall adjacent to the two bedrooms at the first floor north unit needs to be relocated due to proximity to HVAC diffuser air flow, remainder of building is okay.
BLD07-01043 FIRE-Final Inspection8/28/20078/28/20078/28/2007 11:18:05 AMPPASS
Fire life safety passed.
BLD07-00981 FIRE-Sprinkler Rough-in8/27/20078/28/20078/28/2007 10:59:53 AMANR
Intended for life safety inspection, need project related fire alarm and sprinkler finals prior to fire life safety approval.
BLD07-00292 FIRE-Conference8/27/20078/28/20078/28/2007 10:57:14 AMADONE
On site conference to discuss project scheduling, required exits, exit signage, and duct smoke detection.
FIR07-00643 INSP-Final Inspection8/27/20078/28/20078/27/2007 10:40:55 AMPPASS
Final fire sprinkler inspection passed, permit finaled.