BLD07-01107
| FIRE-Final Inspection | 8/28/2007 | 8/28/2007 | 8/29/2007 8:25:48 AM | P | PASS |
|
|
life safety passed
|
BLD05-03032
| FIRE-Final Inspection | 8/28/2007 | 8/28/2007 | 8/28/2007 4:03:05 PM | P | PASS |
|
|
LIfe safety passed.
|
FIR05-00536
| INSP-Sprinkler Rough-in | 8/28/2007 | 8/28/2007 | 8/28/2007 4:01:07 PM | P | PASS |
|
|
The overhead piping in the emergency entrance corridor is ok to cover
|
FIR07-00616
| INSP-Sprinkler Rough-in | 8/28/2007 | 8/28/2007 | 8/28/2007 1:56:21 PM | P | PASS |
|
|
The sprinkler piping is ok to cover
|
BLD07-00353
| FIRE-Final Inspection | 8/27/2007 | 8/28/2007 | 8/28/2007 12:51:01 PM | A | PASS |
|
|
Life safety passed.
|
BLD07-00913
| FIRE-Final Inspection | 8/27/2007 | 8/28/2007 | 8/28/2007 12:49:33 PM | A | CANC |
|
|
Need the project related fire alarm passed first. No inspection performed.
|
BLD07-01012
| FIRE-Final Inspection | 8/27/2007 | 8/28/2007 | 8/28/2007 12:48:09 PM | A | PASS |
|
|
It took two trips today but the life safety is finaly finaled.
|
FIR07-00535
| INSP-Final Inspection | 8/28/2007 | 8/28/2007 | 8/28/2007 12:39:58 PM | P | PASS |
|
|
Permit finaled
|
BLD07-01107
| FIRE-Final Inspection | 8/27/2007 | 8/28/2007 | 8/28/2007 12:35:28 PM | A | FAIL |
|
|
There were no approved drawings or review comments on site. The exit signs and emergency lights did work however.
|
FIR07-00517
| INSP-Sprinkler Rough-in | 8/27/2007 | 8/28/2007 | 8/28/2007 12:02:50 PM | A | FAIL |
|
|
The sprinkler rough-in is ok but there have been alot of 90's added into the branchlines and the 1 1/2" main due to vaulted ceilings in each of the apartments. Also no tenting has been done. The sprinkler piping is not to be covered and resubmittals with hydraulic calculations are required prior to cover.
|
FIR07-00539
| INSP-Alarm Testing | 8/27/2007 | 8/28/2007 | 8/28/2007 11:28:17 AM | A | FAIL |
|
|
The previous correction notice still stands. The monometer test did not pass.
|
BLD06-00910
| FIRE-Final Inspection | 8/27/2007 | 8/28/2007 | 8/28/2007 9:16:27 AM | A | PASS |
|
|
Life safety passed.
|
BLD06-00943
| FIRE-Final Inspection | 8/27/2007 | 8/28/2007 | 8/28/2007 9:08:11 AM | A | FAIL |
|
|
The smoke alarm in apartment 104, ground level, does not sound the other smoke alarms when activated. All other smoke alarms work.
|
FIR07-00720
| INSP-Supply line flush | 8/27/2007 | 8/28/2007 | 8/28/2007 8:33:00 AM | A | PASS |
|
|
Underground flush passed.
|