Inspections for the day of: Tuesday, August 28, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-01107 FIRE-Final Inspection8/28/20078/28/20078/29/2007 8:25:48 AMPPASS
life safety passed
BLD05-03032 FIRE-Final Inspection8/28/20078/28/20078/28/2007 4:03:05 PMPPASS
LIfe safety passed.
FIR05-00536 INSP-Sprinkler Rough-in8/28/20078/28/20078/28/2007 4:01:07 PMPPASS
The overhead piping in the emergency entrance corridor is ok to cover
FIR07-00616 INSP-Sprinkler Rough-in8/28/20078/28/20078/28/2007 1:56:21 PMPPASS
The sprinkler piping is ok to cover
BLD07-00353 FIRE-Final Inspection8/27/20078/28/20078/28/2007 12:51:01 PMAPASS
Life safety passed.
BLD07-00913 FIRE-Final Inspection8/27/20078/28/20078/28/2007 12:49:33 PMACANC
Need the project related fire alarm passed first. No inspection performed.
BLD07-01012 FIRE-Final Inspection8/27/20078/28/20078/28/2007 12:48:09 PMAPASS
It took two trips today but the life safety is finaly finaled.
FIR07-00535 INSP-Final Inspection8/28/20078/28/20078/28/2007 12:39:58 PMPPASS
Permit finaled
BLD07-01107 FIRE-Final Inspection8/27/20078/28/20078/28/2007 12:35:28 PMAFAIL
There were no approved drawings or review comments on site. The exit signs and emergency lights did work however.
FIR07-00517 INSP-Sprinkler Rough-in8/27/20078/28/20078/28/2007 12:02:50 PMAFAIL
The sprinkler rough-in is ok but there have been alot of 90's added into the branchlines and the 1 1/2" main due to vaulted ceilings in each of the apartments. Also no tenting has been done. The sprinkler piping is not to be covered and resubmittals with hydraulic calculations are required prior to cover.
FIR07-00539 INSP-Alarm Testing8/27/20078/28/20078/28/2007 11:28:17 AMAFAIL
The previous correction notice still stands. The monometer test did not pass.
BLD06-00910 FIRE-Final Inspection8/27/20078/28/20078/28/2007 9:16:27 AMAPASS
Life safety passed.
BLD06-00943 FIRE-Final Inspection8/27/20078/28/20078/28/2007 9:08:11 AMAFAIL
The smoke alarm in apartment 104, ground level, does not sound the other smoke alarms when activated. All other smoke alarms work.
FIR07-00720 INSP-Supply line flush8/27/20078/28/20078/28/2007 8:33:00 AMAPASS
Underground flush passed.