MEC14-03722
| Final | 8/28/2014 | 8/28/2014 | 8/28/2014 4:42:32 PM | P | PASS |
|
|
Mid afternoon please. Thanks. Phone #: ###-#### >> Inspection requested via web by April Thomas
|
MEC14-03527
| Final | 8/22/2014 | 8/28/2014 | 8/28/2014 4:12:59 PM | P | PASS |
|
|
installer sam ###-#### Phone #: ###-#### >> Inspection requested via web by Dustin Rich
|
MEC14-03603
| Rough-in | 8/28/2014 | 8/28/2014 | 8/28/2014 3:46:01 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN
|
MEC14-03582
| Rough-in | 8/28/2014 | 8/28/2014 | 8/28/2014 3:45:43 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN
|
MEC14-03653
| Final | 8/25/2014 | 8/28/2014 | 8/28/2014 2:48:02 PM | P | PASS |
|
|
installer Brandan ###-#### Phone #: ###-#### >> Inspection requested via web by Dustin Rich
|
MEC14-03720
| Final | 8/28/2014 | 8/28/2014 | 8/28/2014 2:24:17 PM | P | PASS |
|
|
We have a couple registers to install this morning, I will call the inspector as soon as it''s done. Thanks! Phone #: ###-#### >> Inspection requested via web by Floyd Floyd Peek
|
MEC14-03371
| Rough-in | 8/27/2014 | 8/28/2014 | 8/28/2014 1:54:09 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Otero
|
MEC14-03527
| Pressure Test | 8/22/2014 | 8/28/2014 | 8/28/2014 12:51:15 PM | A | PASS |
|
|
p/t is for flue installer sam ###-#### Phone #: ###-#### >> Inspection requested via web by Dustin Rich
|
MEC14-03715
| Rough-in | 8/27/2014 | 8/28/2014 | 8/28/2014 11:17:16 AM | A | FAIL |
|
|
Alberto Phone #: ###-#### - NOT INSTALLED PER PLANS
|
MEC14-03715
| Pressure Test | 8/28/2014 | 8/28/2014 | 8/28/2014 11:16:40 AM | P | PASS |
|
|
Alberto Phone #: ###-#### - 2OLB GAS PRESSURE PASS
|
MEC14-03655
| Rough-in | 8/27/2014 | 8/28/2014 | 8/28/2014 10:55:50 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Otero
|
MEC12-04525
| Mec-Aging Inspection | 8/28/2014 | 8/28/2014 | 8/28/2014 10:46:58 AM | | CANC |
|
|
NO CALLS
|
MEC14-03607
| Pressure Test | 8/25/2014 | 8/28/2014 | 8/28/2014 10:31:16 AM | A | FAIL |
|
|
Call Jason @ ###-#### with any inspection issues. Phone #: ###-#### >> Inspection requested via web by Angie Maguire - 20LB GAS PRESSURE FAIL, GAUGE WON'T ZERO OUT. 5LB FLUE PRESSURE PASS
|
MEC14-03607
| Rough-in | 8/25/2014 | 8/28/2014 | 8/28/2014 10:30:24 AM | A | FAIL |
|
|
Call Jason @ ###-#### with any inspection issues. Phone #: ###-#### >> Inspection requested via web by Angie Maguire - FLEX DUCT FROM UTILITY ROOM EXHAUST FAN IS PINCH OFF. NEED 6" FRESH AIR TO UP STAIRS UNIT PER MANUAL J, RETURN BOOT IN MASTER BEDROOM IS SITTING UP IN THE TRUSSES.
|
MEC14-02916
| Final | 8/27/2014 | 8/28/2014 | 8/28/2014 9:31:38 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss - PRESSURE TEST FAIL, NO AIR BALANCE REPORT ON SITE
|
MEC14-02916
| Pressure Test | 8/27/2014 | 8/28/2014 | 8/28/2014 9:30:58 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Krista Boss - CAN'T LOCATE PRESSURE GAUGE.
|
MEC14-03603
| Rough-in | 8/27/2014 | 8/28/2014 | 8/28/2014 8:50:23 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN - REINSPECTION FEE NOT PAID
|
MEC14-03582
| Rough-in | 8/27/2014 | 8/28/2014 | 8/28/2014 8:49:29 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by GREGORY ANDERSEN - REINSPECTION FEE NOT PAID
|
MEC14-03584
| Final | 8/26/2014 | 8/28/2014 | 8/28/2014 6:26:07 AM | A | CANC |
|
|
>> Inspection requested via web by Joe Bertwell
|