ELE12-03018
| ELE-Aging Inspection | 8/28/2014 | 8/28/2014 | 9/3/2014 12:41:21 PM | | DONE |
|
|
see final
|
ELE14-02385
| Final | 8/27/2014 | 8/28/2014 | 8/28/2014 4:35:04 PM | P | FAIL |
|
|
Please call 30 minutes in advance if possible Phone #: ###-#### Inspection requested via web by Mike Swift NEC 210.8 All 15 and 20 ampere 120 volt receptacles located in commerical kitchen area require GFCI protection and or within 6 ft. of sink or basin
|
ELE14-02345
| Final | 8/27/2014 | 8/28/2014 | 8/28/2014 3:11:18 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot final ok
|
ELE14-01981
| Final | 8/28/2014 | 8/28/2014 | 8/28/2014 3:11:16 PM | P | FAIL |
|
|
Please inspect after 1pm if possible. Call John Lawson (phone # given) for access to building. Phone #: ###-#### Inspection requested via web by Kendra Lanham NEC 210.8 All 15 and 20 ampere 120 volt garage receptacles require GFCI protection NEC 406.12 Tamper resistant receptacles Those locations refered in 210.52
|
ELE14-02298
| Rough-In Permanent Service | 8/27/2014 | 8/28/2014 | 8/28/2014 3:11:15 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tracy Robertson rough-in p/s u/g n ok 4 plex
|
ELE14-02080
| Final | 8/28/2014 | 8/28/2014 | 8/28/2014 3:11:14 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Don Conley final ok
|
ELE14-02081
| Final | 8/28/2014 | 8/28/2014 | 8/28/2014 3:11:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Don Conley final ok
|
ELE14-02372
| Final | 8/28/2014 | 8/28/2014 | 8/28/2014 11:10:09 AM | A | PASS |
|
|
final on highbays Phone #: ###-#### Inspection requested via web by Tim Dunlop job complete, final ok
|
ELE14-02386
| Electrical Rough-In | 8/28/2014 | 8/28/2014 | 8/28/2014 11:08:56 AM | A | PASS |
|
|
rough in on highbays Phone #: ###-#### Inspection requested via web by Tim Dunlop UL liste material, rough-in ok
|
ELE14-02365
| Rough-In Permanent Service | 8/26/2014 | 8/28/2014 | 8/28/2014 10:33:57 AM | A | FAIL |
|
|
Any questions pleas let us know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Service failed NEC 110.9 Interrupting rating required for available fault current. service close to 100 KVA transformer
|
ELE14-02365
| Electrical Rough-In | 8/28/2014 | 8/28/2014 | 8/28/2014 10:31:12 AM | A | PASS |
|
|
Any questions pleas let us know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Rough-in ok cover
|
ELE14-02379
| Final | 8/27/2014 | 8/28/2014 | 8/28/2014 9:16:20 AM | A | PASS |
|
|
final and permanent service for cable tv power supply located ne corner of 5020 pierce park ln .on castle drive side of property.contact ####-#### andy. Phone #: ###-#### Inspection requested via web by andrew dopieralski job complete, final ok
|
ELE14-02379
| Permanent Service | 8/28/2014 | 8/28/2014 | 8/28/2014 9:14:46 AM | A | PASS |
|
|
final and permanent service for cable tv power supply located ne corner of 5020 pierce park ln .on castle drive side of property.contact ####-#### andy. Phone #: ###-#### Inspection requested via web by andrew dopieralski p/s u/g n ok
|
ELE14-02382
| Final | 8/27/2014 | 8/28/2014 | 8/28/2014 8:55:54 AM | A | NR |
|
|
Eric or Catherine ###-####--service off longer than 1 year-please call for access Phone #: ###-#### Not ready for final at this time
|
ELE14-02382
| Permanent Service | 8/28/2014 | 8/28/2014 | 8/28/2014 8:54:24 AM | A | PASS |
|
|
Eric or Catherine ###-####--service off longer than 1 year-please call for access Phone #: ###-#### p/s u/g rec ok
|
ELE14-01576
| Final | 8/27/2014 | 8/28/2014 | 8/28/2014 8:26:28 AM | A | PASS |
|
|
reinspect Phone #: ###-#### Inspection requested via web by Robert Schroder correction done, final ok
|