ELE12-02185
| ELE-Aging Inspection | 8/28/2015 | 8/28/2015 | 9/3/2015 8:15:13 AM | | CANC |
|
|
too busy
|
ELE12-00913
| ELE-Aging Inspection | 8/28/2015 | 8/28/2015 | 9/1/2015 1:10:37 PM | | CANC |
|
|
too busy
|
ELE15-02697
| Electrical Rough-In | 8/26/2015 | 8/28/2015 | 8/28/2015 2:25:31 PM | P | PASS |
|
|
underground; Kevin Phone #: ###-#### u/g phase on concrete pore ok cover
|
ELE15-02560
| Final | 8/27/2015 | 8/28/2015 | 8/28/2015 1:43:22 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by jody mitchell 110.24 available fault current calc shall be field marked-210.64 electrical service areas shall have a 120v receptacle within 50' of electrical equipment-408.36 (d) backfed breakers shall be secured in place (main breaker missing mounting screw-grounding required
|
ELE15-01587
| Final | 8/28/2015 | 8/28/2015 | 8/28/2015 12:46:40 PM | P | PASS |
|
|
Please call homeowner Jay to meet you there ###-####. Thank You Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
|
ELE15-00520
| Final | 8/28/2015 | 8/28/2015 | 8/28/2015 12:46:36 PM | P | PASS |
|
|
Garage code is 6767 Phone #: ###-#### Inspection requested via web by TOM BICANDI final ok
|
ELE15-02744
| Permanent Service | 8/28/2015 | 8/28/2015 | 8/28/2015 10:34:03 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt p/s o/h rec ok
|
ELE15-01881
| Conference | 8/28/2015 | 8/28/2015 | 8/28/2015 10:07:03 AM | P | DONE |
|
|
Ground works Phone #: ###-#### Inspection requested via web by Eric Schroeder discussed panel location over landing
|
ELE15-01881
| Electrical Rough-In | 8/28/2015 | 8/28/2015 | 8/28/2015 10:06:45 AM | P | PASS |
|
|
Ground works Phone #: ###-#### Inspection requested via web by Eric Schroeder u/g for feed to house ok cover
|
ELE15-02741
| Final | 8/27/2015 | 8/28/2015 | 8/28/2015 9:44:32 AM | A | CANC |
|
|
Michael Phone #: ###-#### needed t/s
|
ELE15-02741
| Temporary Service | 8/28/2015 | 8/28/2015 | 8/28/2015 9:44:10 AM | P | PASS |
|
|
Michael Phone #: ###-#### t/s u/g n ok
|
ELE15-02735
| Rough-In Permanent Service | 8/27/2015 | 8/28/2015 | 8/28/2015 9:25:34 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI rough-in ok cover p/s u/g n ok
|
ELE14-00440
| Rough-In Permanent Service | 8/27/2015 | 8/28/2015 | 8/28/2015 9:05:20 AM | A | PASS |
|
|
Daniel Phone #: ###-#### rough-in ok cover p/s o/h n ok
|
ELE15-02738
| Electrical Rough-In | 8/27/2015 | 8/28/2015 | 8/28/2015 8:52:10 AM | A | PASS |
|
|
we should be there by 8:30am Phone #: ###-#### Inspection requested via web by Tim Dunlop verified u/l listing on light fixtures and installation
|